5.2

TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

Key to switch the Inverter ON ( I )
Key for Inverter shutdown ( O )
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.
Key "Load Off"
The key "Load Off" is protected by a transparent cover.
By pressing it, you immediately separate the UPS from the Load.
It is possible to activate the command "Load Off" using the following screen:
COMMANDS / REQUEST TOTAL OFF. See Section 6.5.
Attention:
To reset "Load Off"
Restore the command "Load Off"
by entering the screen:
COMMANDS / RESET TOTAL OFF
the parallel bus (switch Q1 closed), all the units are separated from the load.
The "Load Off" reset must be done only on one unit connected to the parallel bus
(switch Q1 closed).
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
"Load Off" cannot disconnect the UPS from the Load with Q2 closed.
For Parallel System: if "Load Off" is pressed on one unit connected to
NOTE !
Special care must be taken in using this command, in order to
avoid accidental load disconnection.
Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
User Manual LP33 Series 80 & 100 UL S1
Page 21/66