7.1
PROCEDURES FOR SINGLE LP33 Series 80 & 100
7.1.1 Start-up of the LP33 Series 80 & 100
WARNING !
Before connecting hazardous voltages, make sure that:
• The connection to the electrical system has been performed by QUALIFIED
PERSONNEL;
• The equipment frame has been correctly grounded to the main earth;
• Make sure that utility input protection is removed;
• All the panels removed to allow the UPS connection have been correctly reinstalled;
• The UPS switches Q1 and Q2 are OFF (Pos. 0);
• The "Battery Breaker" of the battery cabinet is OFF (Pos. 0).
This procedure must be performed for the first start-up following the installation, with the UPS
completely switched OFF and not powered.
This procedure presupposes that the Load is not yet supplied by the UPS system.
NOTE !
The UPS can be started-up using the Battery Supply in case the Input Utility should be
unavailable.
To avoid an incidental Battery discharge, it is recommended to proceed to the UPS
start-up having the Input Utility available.
Open the front door and make sure that:
All the connections to the input/output terminals of the UPS have been made correctly.
•
The safety screens are fixed in their position.
•
The switches Q1 and Q2 are open (Pos. O) and the "Battery Breaker" of the Battery Cabinet (option) is
•
OFF (Pos. 0).
Q2
Q1
UPS output switch
Q2
Manual bypass switch
Key
Inverter ON
Inverter OFF
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
Q1
Key
Key
Load Off
LEDs on synoptic diagram
LED 1
Utility rectifier OK
LED 2
Utility bypass OK
LED 3
Rectifier ON
LED 4
Discharging battery
LED 5
Booster ON
LED 6
Charge battery ON
LED
Stop Operation
LED 7
Inverter available
LED 8
Inverter ON
LED 9
Q1 closed
LED 10
Automatic bypass ON
LED 11
Manual bypass Q2 ON
LED 12
Load on UPS
LED
LED
Alarm
Operation
Continue ►
User Manual LP33 Series 80 & 100 UL S1
Page 42/66