Configuration
BATTERY CONFIGURATION
Type
Float voltage
Recharge current
Autonomy time
Stop Operation time
Capacity
:
0147 Ah
ESC
Float voltage
Voltage to maintain battery charging (insert the value of single battery string).
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Lead - Acid (VRLA):
Recharge current
Maximum battery recharge current is 40A.
Autonomy time
The autonomy time of the battery.
UPS autonomy on battery mode at full load condition.
This value is calculated based on the battery type, capacity and number of cells.
2 x 72 cells
UPS Model
147Ah
(24 blocks)
15
LP33 Series 80
9
LP33 Series 100
Autonomy time for battery supplied by GE UPS manufacturer.
Stop Operation time
Residual battery autonomy time before UPS forced shutdown. Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells
Number of cells of the battery (insert the value of single battery string).
Lead - Acid (VRLA): 72 cells.
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery
manufacturer.
Configuration
CONFIGURATION
Save and exit ?
Yes
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
BATTERY CONFIGURATION screen
:
Lead Acid
:
164 V
:
29 A
Type
:
009 min
:
003 min
Cells
: 72
2.27 Vdc for cell
Autonomy times for lead acid batteries (VRLA)
Autonomy at full load at PF=0.9
Battery with expected trickle life 10 years
2 x 147Ah
(48 blocks)
41
30
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done
only by a GE SERVICE PERSON as it requires an access code.
Battery type (Lead Acid).
Lead - Acid
72 cells x 2.27 Vdc = 164 Vdc
U floating = 164 Vdc (2.27 Vdc - cell)
3 x 147Ah
4 x 147Ah
(72 blocks)
(96 blocks)
65
92
52
70
Sealed Battery (VRLA).
5 x 147Ah
6 x 147Ah
(120 blocks)
(144 blocks)
113
132
92
108