GE LP33 Series 80 User Manual page 37

Lp33 series 80 & 100kva / 208vac ul / s1
Table of Contents

Advertisement

Home\Setup\User
MODEM
Tel 2
Tel 2 enabled
Tel 3
Tel 3 enabled
Tel 4
Tel 4 enabled
Tel 4
It records the fourth dial-out number.
Tel 4 enabled
This parameter Y/N specifies if the fourth telephone number will be used for dial-out.
Home\Setup\User
DISPLAY
UPS name
Language
Contrast
Home\Setup\User
ECO MODE
Enabled
DAY OF WEEK
d1
d2
d3
d4
HOURS / DAY
24
24
12
12
In order to check the inverter function, at least 1 minute of VFI mode must be programmed during the week (the
Y/N parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI mode is not respected, the ECO Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.
DAY OF WEEK (d1 to d7): Enabling time in function of weekdays
For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when
the UPS is operating in ECO Mode.
The hour is given in 24-hour format.
These intervals are defined by:
ECO Mode START:
The hour of the day after which the ECO Mode is enabled.
The ECO Mode is enabled until the following ECO Mode STOP time is reached (the ECO Mode
STOP time of the same day if this is later than the ECO Mode START time, the ECO Mode
STOP time of the following day otherwise).
ECO Mode STOP:
The hour of the day before which the ECO Mode is enabled.
The ECO Mode is enabled starting from the preceding ECO Mode START time (the ECO Mode START time of the
same day if this is earlier than the ECO Mode STOP time, the ECO Mode START time of the previous day otherwise).
Identical times for ECO Mode START and ECO Mode STOP maintain the existing mode only in case the previous
command was ECO Mode START and the following command will be ECO Mode STOP.
HOURS / DAY:
The number of ECO Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation
mode parameter window (ceiling value).
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
2
:
N
:
:
3
:
N
:
4
:
N
:
LP Series
:
ENGLISH
:
N
d5
d6
d7
12
12
12
Modem screen 2
Tel 2
It records the second dial-out number.
Tel 2 enabled
This parameter Y/N specifies if the
second telephone number will be used for dial-out.
Tel 3
It records the third dial-out number.
Tel 3 enabled
This parameter Y/N specifies if the third
telephone number will be used for dial-out.
LCD Display screen
UPS Name
The user can choose the name of the UPS
model shown on the main page (max. 9 characters).
Language
This parameter allows the choice of language
used to display the information.
Valid choices are: English, German, Italian, Spanish, French,
Finnish, Polish, Portuguese, Czech, Slovakian, Chinese,
Swedish, Russian and Dutch.
Contrast
This parameter controls the contrast of the
LCD screen in ten steps (0 – 9).
ECO MODE screen
This screen is enabled only for a single UPS, not for an RPA
Parallel System.
Enabled
This parameter (values Y/N) enables or
disables the operation in ECO Mode.
If the value is Y and the current time is in the interval for the
current day, the ECO Mode is active.
The activation / deactivation of ECO Mode is indicated each
time in the event list.
Page 37/66
User Manual LP33 Series 80 & 100 UL S1