6.0
S
PECIFICATIONS
General & Environmental
Unit Rating
Compliant Safety Standards
Conducted and Radiated EMC Levels
Compliant Immunity Standards
Mechanical
Width
Dimensions
Depth
Height
Environmental
Operating Temperature (max)
Relative Humidity
Maximum operating altitude
Nominal heat dissipation
Acoustic noise level
Input Data
Nominal input voltage
Minimum Voltage
Range (Typical)
Power factor
Input frequency (nominal)
Input frequency range
Battery Module
Number of lead acid batteries
Number of battery cells
Maximum charge current (full load)
Nominal Voltage
Recharge Time
Output Data
Output voltage
Voltage regulation
Voltage stability (100% step load)
Recovery time
Voltage distortion
Output frequency
Efficiency at 100% load
Output overload capability
6.1
Product Warranty Registration
To register for warranty protection:
• Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
Units
kVA
4
kW
2.8
Units
8 Bay
20 (508)
in (mm)
28 (711)
40 (1016)
Units
F (C)
%
ft. (m)
BTU/Hr
1,062
dBA
Units
VAC
Operating voltage range is variable based on output loading percentages
% UPS Load
80 – 100%
60 – 80%
30 – 60%
0 – 30%
Cos Ø
Hz
Hz
Units
A
VDC
Hrs
Units
VAC
%
%
msec
%
Hz
%
%
37
Configuration
8
12
5.6
8.4
UL 1778; c-UL
FCC Part 15, Class A
IEEE C62.41, Category B
32° - 104° (0° - 40°)
0-95% non-condensing
10,000 (3,000)
2,124
3,186
<62 @ 1 meter
208 or 240
>.98
60
40-70
10
60
3
120
Typically 6 (to 90% capacity)
208/120 or 240/120
±3
±7
96
<3 THD, linear load
<7 THD, non-linear load
60
89
110 - 125% for 10 min
126-150% for 10 sec
151 - 200% for 2 cycles
Specifications
16
11.2
12 Bay
20 (508)
28 (711)
54 (1372)
4,248
Input Voltage
170 VAC
144 VAC
127 VAC
110 VAC
Need help?