HearthStone Tucson 8702 ST Owner's Manual page 19

Gas-fired direct-vent heater installation & operating instructions
Table of Contents

Advertisement

Hearthstone Quality Home Heating Products, Inc.
Please refer to Figure 10 and Photos 13 & 14 to
adjust your vent restrictor accordingly
All termination caps must be no less than 18"
(457mm) horizontally from any roof or vertical
surface. See Figure 6.
The termination must fall within the chart in
Figure 10.
The maximum vertical run is 35'
The vent/air intake termination clearances above the
high side of an angled roof are as follows:
Roof Pitch
Feet
Flat to 6/12
1
7/12 to 9/12
2
10/12 to 12/12
4
13/12 to 16/12
6
17/12 to 21/12
8
Figure 6: Termination Cap clearances
Prefabricated & Fireplace Chimney
Installations
The Tucson 8702 is approved for use with direct
vent chimney conversion kits in masonry or
prefabricated
solid
fuel
following installation requirements must be followed:
The termination must fall within the chart shown
in Figure 10.
In a masonry chimney, a fireclay liner or listed
steel liner, must be present the entire length of
the chimney.
The maximum length of vent is 35'.
Meters
0.3
0.6
1.2
1.8
2.4
listed
chimneys.
The
The liner must have an inside dimension or
diameter 6" or greater.
Prefabricated chimneys must be UL103 or ULC
S-629 listed and have a minimum INSIDE
diameter of 6". Prefabricated chimneys must be
listed for the specific manufacturer's conversion
kit.
The use of an existing chimney as an air intake is
not listed under the ANSI Z21.88-1999-CSA 2.33-
M99 test methods; this installation has been tested
and approved by Intertek Testing Services with an
appropriate test.
jurisdiction must be consulted prior to proceeding
with this installation method.
Horizontal Termination
The termination must fall within the area shown
in Figures 6 & 7.
A minimum of 9" rise is required either directly
off the heater or with the use of a minimum of a
14" snorkel.
Use a vinyl siding Stand-Off when installing
against vinyl siding. The termination cap must
not be recessed into the wall or siding. Do not fill
air spaces with any type of insulation material.
A minimum 10" X10" square hole is necessary
for proper pipe clearance through a wall,
provided the vent is positioned to maintain 2"
minimum clearance at the top. A 1" minimum
clearance must be maintained to combustible
materials around the other sides.
All horizontal terminations must also comply with
the
clearance
structures outlined in Figure 6.
Horizontal sections require a 1/4" rise every 12"
of horizontal run.
NOTE: For each 90
the allowable horizontal run. For Canadian
installations: remove 4' from the allowable
horizontal run.
At minimum vertical rise, maximum horizontal
run is 10'. (If a 14" snorkel termination is used a
maximum
horizontal
applicable.)
WARNING: FAILURE TO USE ONLY PARTS
SPECIFICALLY APPROVED FOR USE WITH THIS
APPLIANCE
MAY
DAMAGE OR PERSONAL INJURY.
19
Tucson DX/ST Model 8702
The code authority having
specifications
to
adjacent
0
elbow after 2, remove 5' from
run
of
10'
is
RESULT
IN
PROPERTY
also

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tucson 8702 dxTucson dxTucson st

Table of Contents