C. Install the Termination Cap
Note: To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.
WARNING
Fire Risk
The minimum overlap of cap to pipe
MUST be met or chimney may separate
from cap.
Separation allows sparks, heat and embers
to escape.
Install the chimney sections up through the chase
enclosure. When using a TR344 Round Termination
Cap, the uppermost top section of pipe must extend 6 in.
(152 mm) above the top of the fl ashing collar to allow
installation of the storm collar and termination cap. See
Figure 6.5.
Minimum 1-1/2 in. (38 mm) overlap of cap over pipe
6 in. (152mm) min.
Flashing Collar
Figure 6.5
Installing a TR344 Round Termination Cap
For installations utilizing a TR342 Round Telescoping
Termination Cap, the uppermost chimney section must be
below the top of the chase top, but not more than 14-1/2 in.
(368 mm) below the top of the chase top. Minimum overlap
of chimney and termination cap must be 1-1/2 in. (38 mm).
See Figure 6.6.
Flashing Collar
Top of Pipe
Figure 6.6
Installing a TR342 Round Telescoping Termination Cap
Storm Collar
2 in. (51 mm) min.
2 in. (51 mm) min. collar
Storm Collar
2 in. (51 mm) min.
14-1/2 in. (368mm) max.
1-1/2 in. (38 mm) min.
overlap
Heatilator • EL36/EL42 • 4044-132 Rev P • 02/07
For installations utilizing an ST375 Square Termination
Cap the last chimney section must not be more than
4-1/2 in. (114 mm) below the chase top. See Figure 6.7.
Cap Standoff
1-1/2 in.
(38 mm) min.
overlap
Top of Pipe
Figure 6.7
Installing an ST375 Square Termination Cap
For installations utilizing a TS345/TS345P Square
Termination Cap, the uppermost chimney section must
not be more than 3 in. (76 mm) below the chase top. See
Figure 6.8
Flashing
Collar
1-1/2 in.
(38 mm)
Top of Pipe
min.
overlap
Figure 6.8
Installing a TS345/TS345P Square Termination Cap
Flashing Collar
2 in. (51 mm) min.
4-1/2 in.
(114 mm)
max.
2 in.
(51 mm)
min.
3 in.
(76 mm)
max.