C. Securing the Vent Sections
Vertical runs of SLP pipe must be supported every 8 ft.
(2.44 m).
Horizontal sections of vent must be supported every 5 ft.
(.52 m) with a vent support or plumber's strap.
Wall shield firestops may be used to provide horizontal
support.
Vent support or plumber's strap (spaced 120° apart)
may be used for support. See Figures 0.4 and 0.5.
SLP ceiling firestops have tabs that may be used to
provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxi-
ation! Improper support may allow vent to sag and
separate. Use vent run supports and connect vent
sections per installation instructions. DO NOT allow
vent to sag below connection point to appliance.
Figure 10.4 Securing Vertical Pipe Sections
Figure 10.5 Securing Horizontal Pipe Sections
D. Disassemble Vent Sections
Rotate either section (see Figure 0.6) so the seams
on both pipe sections are aligned as shown in Figure
0.7.
Pull carefully to separate the pieces of pipe.
Figure 10.6 Rotate Seams for Disassembly
Figure 10.7 Align and Disassemble Vent Sections
Heatilator • Eclipse • 4049-229 Rev I • 08/09