Model
5. Battery & Charger
5.1 Types
5.2 Number of Battery
5.3 Protection
5.4 Recharge Voltage
5.5 Recharge Current
- Standard Mode
5.6 Battery Leakage Current
5.7 Battery Low Voltage Alarm
5.8 Battery Shutdown Voltage
5.9 Back-up Time
6. Operation
6.1 Transfer Time
- On line Mode
- Main Power Failure
- Main Power Recover
- Inverter To Bypass
- Bypass To Inverter
- Economy Mode
- Main Power Recover
- Inverter To Bypass
- Bypass To Inverter
- Main Power Failure
6.2 Audible Noise
7. Indications
7.1 LED Status Mimic Diagram
7.2 LCD Display
8. Communications
8.1 RS232
8.2 Remote Emergency Power Off
8.3 Dry-Contact
8.4 SNMP Function (Optional)
8.5 External Battery Pack Detection
6KVA
Sealed Lead Acid
12Vdc battery x 20 PCS
30A/600V x 2pcs FUSE
Floating 271Vdc/ Boost 280Vdc
0.7A at 250Vdc (175W)
220Vdcr 3
212Vdcr 3 (discharge exceed 1hour)
7 Minutes (4200W)
8ms (Typical)
53 dBA
Normal, Battery, Bypass, Fault
Refer to Chapter 5.
Refer to Chapter 6.
Refer to Chapter 6.
Refer to Chapter 6.
Refer to Chapter 6.
Refer to Chapter 6.
9
12KVA
8Hrs 90
1.4A at 250Vdc (350W)
1mA
3 Minutes (8400W)
0ms
0ms
1ms
1ms
0ms
1ms
1ms
65 dBA