Delta Electronics Amplon Family User Manual

N series, single phase 6/12 kva

Advertisement

Quick Links

The power behind competitiveness
Delta UPS - Amplon Family
N Series, Single Phase
6/12 kVA
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta Electronics Amplon Family

  • Page 1 The power behind competitiveness Delta UPS - Amplon Family N Series, Single Phase 6/12 kVA User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2013 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, infor- mation, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS 1. IMPORTANT SAFETY INSTRUCTIONS................... 1 2. INTRODUCTION ..........................3 2-1 FUNCTIONS AND FEATURES....................3 2-2 FRONT CONTROL PANEL......................4 2-3 REAR CONTROL PANEL......................5 3. TECHNICAL SPECIFICATION ......................8 4. INSTALLATION ..........................11 4-1 UNPACKING AND INITIAL INSPECTION ................. 11 4-2 STORAGE AND BATTERY MAINTENANCE ................
  • Page 4: Important Safety Instructions

    1. IMPORTANT SAFETY INSTRUCTIONS z This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. z Install the on line UPS in a well ventilated area, away from flammable liquids and gases. Do not let the unit come in contact with water.
  • Page 5 z ATTENTION, hazardous through electrical shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through supply from the batteries. The battery supply should be therefore disconnected in the plus and minus pole of the batteries when maintenance or service work inside the UPS is necessary.
  • Page 6: Introduction

    2. INTRODUCTION 2-1 FUNCTIONS AND FEATURES z A True ON LINE design. The UPS insures the critical power protection for your mission-critical equipment at all times. z Wide input range of power supply that reduces discharge rate of battery. z A smart charger design for auto equalizing charge to shorten charging time. z Equipped with RS232 port and Dry-contact interface, using the power management software “UPSentry Smart 2000”...
  • Page 7: Front Control Panel

    2-2 FRONT CONTROL PANEL FRONT CONTROL PANEL 1. INVERTER ON BUTTON Press the “ON” button for 3 seconds to activate the inverter. 2. INVERTER OFF BUTTON Press the “OFF” button for more than 3 seconds to disable the inverter. 3. FUNCTION BUTTON - In BYPASS/ECONOMY/ON LINE/BATTERY mode, press the up ( ) or down ( ) button to view information on load, voltage and frequency of bypass, input and output, battery and charger.
  • Page 8: Rear Control Panel

    2-3 REAR CONTROL PANEL BATT. NO. EMERGENCY POWER OFF RS-232 SNMP CONTACT INPUT BREAKER MANUAL BYPASS 240VDC 20A 6KVA...
  • Page 9 BATT. NO. EMERGENCY POWER OFF RS-232 SNMP CONTACT MANUAL BYPASS 240VDC 40A 12KVA...
  • Page 10 1. MANUAL BYPASS SWITCH: To change power load from static bypass to directive bypass while maintaining UPS without any power interruption. 2. INPUT TERMINALS: To connect the AC mains input. 3. OUTPUT TERMINALS: Connection of the load terminals is supported by UPS. 4.
  • Page 11: Technical Specification

    3. TECHNICAL SPECIFICATION Model 6KVA 12KVA 1. Power 1.1 Power (VA) 6000VA 12000VA 1.2 Power (W) PF=0.7 4200W 8400W 2. Output Waveform Sine wave 3. Input 3.1 Input Voltage 220Vac, single phase 3.2 Input Current 27.3A 54.5A  200A - Inrush Current ! 0.99 (At Normal Line and Full Load) - Power Factor 3.3 Efficiency (Full Resistance Load)
  • Page 12 Model 6KVA 12KVA 5. Battery & Charger 5.1 Types Sealed Lead Acid 12Vdc battery x 20 PCS 5.2 Number of Battery 30A/600V x 2pcs FUSE 5.3 Protection Floating 271Vdc/ Boost 280Vdc 5.4 Recharge Voltage 5.5 Recharge Current 8Hrs 90 0.7A at 250Vdc (175W) 1.4A at 250Vdc (350W) - Standard Mode 5.6 Battery Leakage Current...
  • Page 13 Model 6KVA 12KVA 9. Connection 9.1 Input Terminal Block 60A/600V 4 Pin x1 9.2 Output Terminal Block 60A/600V 7 Pin x1 9.3 Extended Battery I/P Socket 10. Manual Bypass Switch Function 11. Outlook 11.1 Dimension - Depth (D) 581mm/22.87 inches 630mm - Width (W) 280mm/11.02 inches 280mm - Height (H)
  • Page 14: Installation

    4. INSTALLATION 4-1 UNPACKING AND INITIAL INSPECTION Carefully unpack and inspect the UPS upon receipt. If there is damage or anything is missing from the shipment, contact the dealer from whom you purchased the unit and save the packaging for future shipment. The packaging is recyclable, save the box and packing material for reuse.
  • Page 15 Required Protective Devices and Cable Selection Refer to the following table on recommended cables and upstream protection: Model Rated Input Cable Rated Output Cable Upstream Circuit-Breaker 6 KVA 8AWG or 8mm 8AWG or 8mm D curve – 40A 12 KVA 6AWG or 14mm 6AWG or 14mm D curve –...
  • Page 16: Handling

    4-4 HANDLING z The unit is fitted with wheels for moving it over a short distance. It is stabilized by four feet at both side. For safety reason, secure the unit by releasing the feet. Refer to Fig.1 & 2 or Fig.1 & 3. z The UPS should always have a clearance space of 300mm at the rear and 100mm on its side.
  • Page 17: Operation

    5. OPERATION 5-1 POWER ON/OFF INVERTER Power On Inverter Switch on the AC input breaker on rear control panel, and the load will be energized. z When the AC input is normal, press the inverter “ON” button on front control panel for 3 seconds.
  • Page 18: Error Messages

    z After diagnostic test, the load is supplied by the inverter; if the diagnostic test fails, the error messages will be shown as below. ERROR MESSAGES BAD BATTERY BAD BATTERY SHUT DOWN CHARGER FAILURE CHARGER FAILURE SHUT DOWN DC BUS FAILURE DC BUS FAILURE SHUT DOWN INVERTER FAILURE...
  • Page 19: Lcd Function Selection Switch

    5-2 LCD FUNCTION SELECTION SWITCH In BYPASS/ECONOMY/ON LINE/BATTERY mode, press the up ( ) or down ( ) button on front control panel to view different power readings on LCD. OPERATION IN BYPASS MODE OPERATION IN ECONOMY MODE BYPASS MODE ECONOMY MODE LOAD = XXX% X.XXKW LOAD = XXX% X.XXKW...
  • Page 20: Parameter Set-Up Mode

    5-3 PARAMETER SET-UP MODE Press both up ( ) and down ( ) buttons altogether for 3 seconds, then the UPS will enter SET-UP mode. SET-UP MODE UPS SET-UP EXIT ENTER OUTPUT VOLTAGE SCROLL SELECT OUTPUT VAC=220V SCROLL SELECT S e l e c t o u t p u t v o l t a g e R e t r u n t o s e t i n i t i a l OUTPUT VAC=230V SCROLL...
  • Page 21 EX T EN D B A TT E R Y SC R OLL SELEC T E XT E N D = N O N E S C R OL L S E LE C T TO UPS SET-UP S e l e c t e x t e n d b a t t e r y R e t r u n t o s e t i n i t i a l EXTEND = 010 A h SCROLL...
  • Page 22: Operation On Bypass Voltage Beyond Allowable Range

    5-4 OPERATION ON BYPASS VOLTAGE BEYOND ALLOWABLE RANGE The UPS can automatically detect the voltage in bypass mode. The protection range is +15%~-20%. When the bypass voltage is beyond protection range, the UPS will not supply output power to the load. When the bypass voltage is higher than 115% of rating voltage, the UPS will alarm and will not supply output power to the load.
  • Page 23: Verifying The Battery Status

    5-6 VERIFYING THE BATTERY STATUS The battery status is shown as below: Battery Status Buzzer of Back-up Status LCD Display Full BATTERY MODE Beep per 2 seconds BATT=XXXVXXX% LOW BATTERY Beep per 0.5 seconds LOAD=XXX% X.XXKW LOW BATTERY Under Long beep SHUTDOWN 5-7 OPERATION OF MANUAL BYPASS SWITCH The manual bypass switch is used for maintenance.
  • Page 24: Communication Interface

    6. COMMUNICATION INTERFACE 6-1 RS232 INTERFACE A 9-pin female SUB-D connector is provided on rear panel of UPS to transmit the UPS signals to the computer. Using the Delta “UPSenrty Smart 2000” software allows users to check the power status. The details on signals are shown as below. Pin Assignment: z Load level z Pin 2: TXD (Transmit Data)
  • Page 25: Dry Contact

    6-3 DRY CONTACT The sub-D communication port (9-pin female type) is used for powering on/off the UPS by external control signal. UPS can also transmit its status through this port. Refer to the following Dry contact table. Pin 8, 3 Pin 1, 3 Pin 6, 3 Pin 5, 3...
  • Page 26: Snmp Card (Optional)

    6-4 SNMP CARD (OPTIONAL) SNMP network interface is a powerful tool for remote control and UPS monitoring. BATT. NO. EMERGENCY POWER OFF RS- 232 SNMP CONTACT MANUAL BYPASS 240 VDC 40A NOTE: For more information on SNMP card (optional), contact your local dealer.
  • Page 27: Detection For Quantity Of External Battery Pack

    6-5 DETECTION FOR QUANTITY OF EXTERNAL BATTERY PACK When the UPS is connected with Delta’s standard battery packs, you can detect the total battery capacity by linking the UPS to the battery pack. BATTERY 2 BATTERY 1 NOTE: This function can detect up to a maximum of two external battery packs.
  • Page 28 Warranty Seller warrants this product, if used in accordance with all applicable instruc- tions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty pe- riod, Seller will repair or replace the product at its sole discretion according to the failure situation.