Technical Specification - Delta Electronics Amplon Family User Manual

N series, single phase 6/12 kva
Table of Contents

Advertisement

3. TECHNICAL SPECIFICATION

1. Power
1.1 Power (VA)
1.2 Power (W) PF=0.7
2. Output Waveform
3. Input
3.1 Input Voltage
3.2 Input Current
- Inrush Current
- Power Factor
3.3 Efficiency (Full Resistance Load)
- On line Mode (AC to AC)
- Economy Mode
3.4 Input Frequency
3.5 Input Protection Circuit Breaker
4. Output
4.1 Output Voltage
- RMS Voltage
- Static Regulation
4.2 Harmonic Distortion
4.3 Overload Capability
4.4 Overload Release
4.5 Inverter Short Circuit Protection Current
4.6 Short Circuit Protection
4.7 Output Frequency
4.8 Output Protection Circuit Breaker
- Bypass (Outside Installation Capacity)
- Inverter
4.9 Crest Factor
Model
6KVA
6000VA
4200W
220Vac, single phase
27.3A
! 0.99 (At Normal Line and Full Load)
88% (Full linear load)
94% (Full linear load)
50/60Hz±0.5,1, 2, 3, 4, 5 Hz (Programmable)
40A (1 pole x 1)
120V/220Vac, single phase
102% Continuous
102%~125%: 1 Minute
125%~150%: 30 Seconds
! 150%: Immediate
90r 5
90A
Shutdown and no output
50/60Hz r 0.5Hz (Battery mode)
40A(1pole*1)
Electronic protection
8
12KVA
12000VA
8400W
Sine wave
54.5A
 200A
63A (1 pole x 1)
r 2
 5%
(Rated Load)
150A
63A(1pole*1)
2.7:1