Check Network Wiring - Crestron Isys TPS-6 Operation Manual

5.7” tilt touchpanel
Hide thumbs Also See for Isys TPS-6:
Table of Contents

Advertisement

Crestron TPS-6
Use the Right Wire
Calculate Power
Operations Guide – DOC. 6945A
TPS-6 Troubleshooting (Continued)
TROUBLE
POSSIBLE CAUSE(S)
Unexpected
Touchpanel is
response from
incorrectly calibrated.
touchpanel.
TPS-6 boots up
Invalid VT Pro-e project
with message
or no VT Pro-e project is
saying "Your
loaded.
desired page was
not found."

Check Network Wiring

In order to ensure optimum performance over the full range of your installation
topology, Crestron Certified Wire and only Crestron Certified Wire may be used.
Failure to do so may incur additional charges if support is required to identify
performance deficiencies because of using improper wire.
CAUTION: Use only Crestron power supplies for Crestron equipment. Failure to
do so could cause equipment damage or void the Crestron warranty.
CAUTION: Provide sufficient power to the system. Insufficient power can lead to
unpredictable results or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the system
(www.crestron.com/calculators).
When calculating the length of wire for a particular Cresnet run, the wire gauge and
the Cresnet power usage of each network unit to be connected must be taken into
consideration. Use Crestron Certified Wire only. If Cresnet units are to be daisy-
chained on the run, the Cresnet power usage of each network unit to be daisy-
chained must be added together to determine the Cresnet power usage of the entire
chain. If the unit is home-run from a Crestron system power supply network port, the
Cresnet power usage of that unit is the Cresnet power usage of the entire run. The
wire gauge and the Cresnet power usage of the run should be used in the following
equation to calculate the cable length value on the equation's left side.
Cable Length Equation
Where:
L = Length of run (or chain) in feet
40,000
R = 6 Ohms (Crestron Certified Wire: 18 AWG (0.75 MM ))
L <
R x P
P = Cresnet power usage of entire run (or chain)
Make sure the cable length value is less than the value calculated on the right side of
the equation. For example, a Cresnet run using 18 AWG Crestron Certified Wire and
drawing 20 watts should not have a length of run more than 333 feet. If Cresnet HP
is used for the same run, its length could extend to 1250 feet.
NOTE: All Crestron certified Cresnet wiring must consist of two twisted pairs. One
twisted pair is the +24V conductor and the GND conductor and the other twisted
pair is the Y conductor and the Z conductor.
Isys™ 5.7" Tilt Touchpanel
CORRECTIVE ACTION
Recalibrate the touchscreen
(refer to "Configuring the
Touchpanel" which starts on
page 11 and "CALIBRATION
MENU" on page 12).
Load/reload VT Pro-e project
using Crestron Toolbox.
or 1.6 Ohms (Cresnet HP: 12 AWG (4 MM ))
Isys™ 5.7" Tilt Touchpanel: TPS-6 • 41