ADDENDUM #2 Interior Masonry Chimney Conversions
•
Follow the requirements and use the equipment listed in the illustration below to install this appliance
into an interior masonry chimney.
•
Maximum vertical rise is 40'
•
Minimum vertical rise is 10'
•
See the chart on page 13 for determining the correct restrictor position.
NOTE: these restrictor positions are based upon lab tests. The ideal restrictor position may vary
slightly.
Interior Masonry Chimney
Standard Masonry Fireplace
The entire chimney system
must be air-tight. Seal the
connector cover and inspect
the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
Travis Industries
Installation Addenda
The entire chimney system
must be air-tight. Make sure to
seal the flashing, clean-out,
and thimble connection, and to
inspect the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
#990 90° Elbow
Co-Axial Straight
Lengths
1 0 0 - 0 1 1 5 9
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit
#711 Flex Liner (4" dia.)
(or other UL 1777 Gas
Liner)
Connector with Cover
(included in #934 Masonry
Conversion Kit)
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit)
#711 Flex Liner (4" dia.)
(or other UL 1777 Gas Liner)
Connector (included in #934
Masonry Conversion Kit)
secured and sealed to
block-off plate.