8 TROUBLESHOOTING

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see fig. 3.3.5.a/b) and be sure that the
UPS is not overloaded.
The following chart is a simple troubleshooting checklist. If the suggested solution does not succeed, or if
the information is insufficient to solve the problem, please contact your dealer or consult
www.GEDigitalEnergy.com
PROBLEM
No display
No alarm
(UPS switched off)
Mains indicator not illuminating,
acoustic alarm intermittent
Mains indicator not illuminating,
mains voltage present, acoustic
alarm intermittent
Alarm LED illuminated,
continuous acoustic alarm
Delivered runtime less than
specified
Last load bar LED is lit, acoustic
alarm intermittent
No communication between
UPS and PC
modifications reserved
POSSIBLE CAUSE
Mains switched off
No mains voltage present
Input fuse blown or circuit
breaker tripped
No mains voltage present
Input fuse blown or circuit
breaker tripped
UPS failure
UPS over-temperature
Overload at UPS output
Battery extension fuse switch is
in 'Open' position
Batteries are not fully charged
Batteries are defective
Charger is defective
Overload at UPS output
Incorrect communication cable
PC interface defective or being
accessed by another service
Interference on the data cable
40
SOLUTION
Switch on mains supply
Carry out mains inspection,
consult qualified electrician
Replace fuse or reset breaker
Read section 4.4.2 – UPS on
battery
Replace fuse or reset breaker
Contact UPS dealer or go to
www.GEDigitalEnergy.com
Allow UPS to cool down
Reduce UPS load
Switch to 'On' position
Charge batteries for 8 hours and
reconfirm runtime
Contact UPS dealer
Contact UPS dealer
Reduce UPS load
Check whether correct cable is
used
Check if no other software is
accessing the interface
Rearrange cables
User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)