UPStation GXT 3x1
TROUBLESHOOTING GUIDE
PROBLEM
Fault and Bypass
indicators and all load
level LED's are
illuminated
Fault and Bypass
indicators and
diagnostic LED A are
illuminated
Fault and Bypass
indicators and
diagnostic LED B are
illuminated
Fault and Bypass
indicators and
diagnostic LED D are
illuminated
Fault and Bypass
indicators and
diagnostic LED E are
illuminated
Fault indicators and
diagnostic LED A & C
are illuminated
Fault indicators and
diagnostic LED C & E
are illuminated
6.3

Maintenance

The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, non-spillable, lead acid,
and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to
the mains supply.
When storing the UPS for any length of time, it is recommended to apply power to the UPS for at least 24 hours every
four to six months to ensure full recharge of the batteries. In no case should the unit be stored in excess of nine months
without recharge. Periodically, examine the vents on the front and rear of the cabinet, and remove any obstructions from
the surface of the vents.
CAUSE
UPS overloaded or load
Check load level display and
equipment is faulty
remove non-essential loads.
Recalculate load VA and
reduce number of loads
connected to UPS. Check load
equipment for faults.
UPS internal fan has a
Press Alarm silence button.
problem or UPS
Ensure that there are no
shutdown due to
obstructions in front panel
temperature condition.
vents or on rear panel fans;
Load is on bypass
and UPS is not overloaded.
power.
Once the temperature is
reduced, the UPS will restart
and transfer the connected
equipment to inverter power
automatically.
UPS internal DC bus
over voltage
UPS PFC fault.
UPS requires service. Contact
your dealer or technical
support.
UPS inverter fault.
UPS failed the battery
Replace batteries. Contact
test.
your dealer or technical
support.
UPS shutdown due to a
Your UPS has received a
command from the
signal or command from the
communications port(s)
attached computer. If this was
inadvertent, ensure the
communication cable used is
correct for your system. For
assistance, contact your dealer
or technical support.
SOLUTION
(06/02)
Chapter 6 – Troubleshooting
Page 21