Table 10. Device status
Sensor display
Wireless Builder display
OUT SVC
OOS
CFG ERR
Configuration Error
LOW BAT
Low Battery
NO RADIO
Radio Interprocessor
Comm Error
BAD RADIO
Sensor Radio SPI
SPI
Communication Failure
BAD RADIO
EEPROM SPI
EEPROM
Communication Failure
RADIO WDT
WDT Reset Occurred
RESET
BAD RADIO
Radio Circuitry Failure
The following status messages have multiple meanings. Refer to Wireless Builder Device Status for exact cause.
E FAIL
A/D Failure
E FAIL
Electronics Failure
E FAIL*
NVM Fault*
E FAIL*
Program Memory Fault*
E FAIL*
RAM Fault*
INP FAIL
Input Failure
INP FAIL
A/D Failure
Definition
All channels are out of
service
Configuration check error
Battery voltage critically
low
Radio board is not
accessible
Radio detected loss of
communication with
sensor board over the
inter-processor
communication link
Radio EEPROM SPI
communication failure
Radio watch dog timeout
detected
Radio circuitry has failed
Diagnostics detected
defect with analog to
digital converter
Electronic failure
detected on sensor
board. Could be caused
by one of the status
items marked by *
Startup diagnostics
detected defect in sensor
non-volatile memory
Startup diagnostics
detected defect in sensor
read only memory
Startup diagnostics
detected defect in
processor random
access memory
Input error
Diagnostics detected
defect with analog to
digital converter
Issue 3
5.3. Sensor PV Display
What to do
Restore mode to auto in wireless builder
Database is corrupted. Cold start and reload
configuration
Replace batteries as soon as possible. See
page 35
Restart both the radio and sensor. If condition
persists, sensor module must be replaced
Restart both the radio and sensor. If condition
persists, sensor module must be replaced
The radio will not be able to perform firmware
upgrades but will operate normally using
installed code. Sensor module should be
replaced
Restart both the radio and sensor. If condition
persists, sensor module must be replaced
The radio processor detected error on internal
radio circuitry. Sensor module must be
replaced
Sensor module must be replaced
Restart both the radio and sensor. If condition
persists, sensor module must be replaced
Sensor module must be replaced
Sensor module must be replaced
Sensor module must be replaced
Check potentiometer connections.
Verify that slip clutch is properly engaged with
input shaft. Check slip clutch operation.
Restart the sensor. If condition persists, sensor
module must be replaced
Sensor module must be replaced