S4 Beam Sensor & brackets

Find Device

How to find a 'Beam receiver' or 'Beam transmitter'

You can find a 'beam transmitter' or 'beam receiver' device on a loop circuit by using the Find Device
function at the control panel.
To speed up the search to find the location of a Beam sensor you must first refer to the 'as fitted wiring
drawings' which provides the address or approximate address of the device on the loop circuit. Enter the
device address at the panel and [Start] the 'find device' function. When the beam sensor is found then its red
LEDs flash.
Procedure for Vigilon panel (Access level 3)
[Test/Eng]
[UserCode]
Params
[Start]
1-8
Params
[E]
[C] [Q]
1-207
[P]
[N] [Q]
To 'find' the previous device select [P] or to
find the next device select [N]. An audible and/or
visual indication will be given at the found device.
Procedure for Nano panel (Access level 4)
Menu
Engineering
Select
Fast Find
4188-968 issue 4_Part 2_07-12_S4 mains interface
[Loop]
<etc>
Enter the loop number on which the
beam sensor is installed
Enter the device address from where
to START 'find'
Loop
Select
Select
Enter a 'Device' from a range 1 to 127
and then scroll to the required device.
Both red LEDs give long flash on either the
'beam receiver' or 'beam transmitter'
to indicate a found device.
[FindDev]
Both red LEDs give long flash on either the
'beam receiver' or 'beam transmitter'
to indicate a found device.
>
Select
To move to
To scroll the
next setting
range
16:15 Mon 16/02/09
Fast Find
Fast Find Enabled: [NO ]
Device Number: [
1]
WARNING: Find will action relay outputs!
Commissioning information
Beam Sensor
Control
>
Back
Back
Beam Sensor
9