Chapter 3 General Specification 3-1; General Specification - LG G3L-PUEA User Manual

Programmable logic controller
Table of Contents

Advertisement

CHAPTER 3 GENERAL SPECIFICATION
CHAPTER 3 GENERAL SPECIFICATION

3.1 General Specification

The General Specification for the communication module of GLOFA series and MASTER-K series is as follows:
No.
Items
1
Use Temperature
2
Storage Temp.
3
Use humidity
4
Storage humidity
5
Vibration-resistant
6
Impact-proof
7
Noise-resistant
Surrounding
8
environment
9
Use altitude
10
Pollution
11
Cooling method
Note
1) IEC(International Electrotechnical Commission) : International civil community that promotes international cooperation
for standardization of electric/electro technology, publishes international standard and operates suitability assessment
system related to the above.
2) Pollution Degree : An index to indicates the pollution degree of used environment that determines the insulation
performance of the device. For example, pollution degree 2 means the state to occur the pollution of non-electric
conductivity generally, but the state to occur temporary
0 ~ 55 °C
−25°C ~ +70 °C
5 ~ 95%RH, no dew
5 ~ 95%RH, no dew
In case of Intermittent vibration
Frequency
Acceleration
10 ≤ f < 57Hz
57 ≤ f ≤ 150Hz
9.8m/s
In case of Continuous vibration
Frequency
Acceleration
10 ≤ f < 57Hz
57 ≤ f ≤ 150Hz
4.9m/s
• Max. impact acceleration : 147 m/s
• Application time : 11ms
• Pulse wave type : semi-sine wave pulse (3 times each direction X,Y,Z)
Square wave
impulse noise
Electrostatic
discharge
Radiant
electromagnetic
field noise
Classi-
Fast transient
fication
/ Bust noise
Voltage
No corrosive gas, no dust
Less than 2,000m
Less than 2
Natural air-conditioning
Table 3.1 General Specification
Specification
Amplitude
0.075mm
2
{1G}
Amplitude
0.035mm
2
{0.5G}
2
{15G}
± 1,500 V
Voltage : 4kV (Touch discharge)
27 ~ 500 MHz, 10 V/m
Power
Digital I/O
modul
(more than 24V)
e
2kV
1kV
electric conduction according to the formation of dew.
3-1
Reference
-
Times
X, Y, Z
IEC61131-2
10 times
each direction
IEC61131-2
LGIS internal
test standard
IEC61131-2
IEC1000-4-2
IEC1131-2,
IEC1000-4-3
Digital I/O
(less than 24V)
IEC1131-2
Analog I/O
IEC1000-4-4
Communication
interface
0.25kV

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G6l-puebG3l-puebG4l-pueaG4l-puebG7l-pbeaG6l-puea

Table of Contents