SERVICE CLEARANCES

Your installer will have provided adequate space around the boiler for safety and servicing access.
CAUTION: Restricted space.
The boiler may overheat.
B Do not restrict this space with the addition of cupboards, shelves etc. next to the
boiler.
Fig. 8
Service clearances
5 mm
600 mm
6 720 644 864a (2010/10)
+ 30 mm
above elbow
5 mm
200 mm
SERVICE CLEARANCES
13

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GREENSTAR i SYSTEM and is the answer not in the manual?

Questions and answers

Martin
March 11, 2025

I can’t get my green star I to stay operating it keeps turning off

User image 67cffd7aae42d
1 comments:
Mr. Anderson
March 11, 2025

The Worcester Greenstar i System boiler may keep turning off due to several possible reasons:

1. No Power – Check if the boiler has a permanent mains supply. Inspect Fuse F1 (2.5A) or Fuse F3 (0.5A) and the transformer. If faulty, replace the control board.

2. No Live Demand – Ensure there is a live demand at ST10-L from an external room thermostat or timer. Some older thermostats may not return proper voltage.

3. Diverter Valve Issue – If the boiler operates without a live demand signal, check that no permanent live feed is present at ST10-L from another source.

4. Incorrect Piping – Ensure the cold inlet and DHW outlet are correctly piped and not crossed.

5. Flow Turbine Issue – If the boiler is not operating during hot water demand, test the flow turbine.

Further troubleshooting may require checking the control board and other electrical components.

This answer is automatically generated