Snmp Command Group - GE Digital Energy 1018959 Operating Manual

Snmp / web adapter
Hide thumbs Also See for Digital Energy 1018959:
Table of Contents

Advertisement

2.2.8 Snmp command group

The snmp command group allows to configure the SNMP Agent for UPS monitoring via SNMP and trap
notification of UPS events and alarms:
Command
Parameters
showsnmp
snmpport
[port]
snmp-server
on | off
syscontact
[contact] (**)
syslocation
[location] (**)
getcommunity
[community]
setcommunity
[community]
(*) Changing the port causes the SNMP Agent to restart. This might have a temporary effect also on trap
notification.
(**) Both parameters have a maximum length of 63 chars. If these parameters contain blanks or special
characters they shall be specified in between double quotation marks ("...") .
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc
Description
Show detailed system information
Set SNMP server listening port (*)
[port] SNMP port
NOTE: Default SNMP port is 161.
Enable/disable SNMP Agent
on
SNMP Agent enabled
off
SNMP Agent disabled
Set the system contact
[contact]
contact person
NOTE: The syscontact parameter is the identification of
the contact person for the managed node.
Set the system location
[location]
location name
NOTE: The syslocation parameter is the identification of
the physical location of the managed node.
Defines the community name for receiving SNMP
information (GET).
[community]
community name
NOTE: The get community name controls access to the
SNMP Agent – the community in the request must match
the getcommunity parameter.
The default value is public.
Defines the community name for writing SNMP
information (SET).
[community]
community name
NOTE: The set community name controls access to the
SNMP Agent – the community in the request must match
the setcommunity parameter.
The default value is private.