Figure 5 InfiniBand Cable Secured with a Releasable Cable Tie
1
2
Caution:
The releasable cable tie should only be hand tight. Do not use a cable tie installation tool and
do not over tighten the releasable cable tie or it might damage the InfiniBand cable.
4.
Leaving approximately 1/4 inch to 3/8 inch coming out of the buckle, clip the excess from
the releasable cable tie. Use one of the clipped-off pieces of cable tie as a tightness gauge
(see callout 1 in
Figure
in
Figure
6) to move freely in the releasable cable tie loop (callout 3 in
to the cable management bracket (callout 2 in
in
Figure
6).
Figure 6 Gauging the Tightness of the Releasable Cable Tie Loop
3
2
5.
Repeat steps 4 and 5 to secure the remaining InfiniBand cables.
6.
Route the InfiniBand cables to the side of the rack and secure them either upward or downward
in the cable management plate. Be sure not to exceed the cable manufacturer's recommended
bend radius for each InfiniBand cable as you route them in the rack.
6) to check that there is room to allow the InfiniBand cable (callout 4
1
3.2 Installing the Releasable Cable Ties for the InfiniBand Cables
Figure
6) with a push button mount (not shown
4
Figure
6) that is secured
1 1