CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION
VOLTAGE RANGE
69.3/120V
120/208V
277/480V
5A CT High End
2.5A Low End
Table 11-2: Calibration Source, Full Scale and Value Settings for Calibration
11.2: Group 2, Functions 0–2—High End Calibration of Voltage Channels, High
and Low End Calibration of Amperage Channels
To change the calibration (high end—Functions 0 and 1):
NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.
MAX
MIN
LM1
LM2
KVAH
KWH
MAX/MIN
VOLTS AMPS
LIMITS
Step 1:
a. Enter Group Level of Programming Mode
(see Chp. 8).
b. Press MAX/MIN/LIMITS until 2. appears in
upper display.
c. Press AMPS to activate the Group.
!A one-digit password is required to continue.
d. Press VOLTS until 5 appears.
e. Press AMPS to select.
68
INPUT SOURCE
120V L-N
AC VOLTS
A
B
C
A
B
C
N
N
N
B
C
A
AC AMPS
A
B
C
N
POWER
PF
KW
KVA
FREQ
KVAR
PHASE
POWER
NEXT
EPM 5000 series Advanced Power Meters
75V
300V
5A
2.5A
MAX
MIN
LM1
LM2
KVAH
MAX/MIN
VOLTS
LIMITS
Step 2:
! Refer to Table 11-1 for Function Number that
corresponds to the area requiring calibration. Calibration
for each area begins with A and then moves to B and C.
a. Press MAX/MIN/LIMITS to change Function number.
GROUP 2 VALUE
1440
1440
0300
2000
1000
AC VOLTS
A
B
C
A
B
C
N
N
N
B
C
A
AC AMPS
A
B
C
N
POWER
PF
KW
KVA
KWH
FREQ
KVAR
PHASE
POWER
AMPS
NEXT
GE Multilin