CHAPTER 4
COMMUNICATION INSTALLATION
4.1: RS-232C
(This section applies to the RS-232C or RS-485.)
All EPM 5300P and 5200P instruments can be equipped with RS-232C or RS-485 communication.
RS-232C communication links a single instrument with a computer or device such as an RTU or PLC. Its
capability is up to 100 feet. A standard 9-pin female serial port connector mounts on the instrument for
direct connection to a computer with a 9-pin cable.
8
9
10
7
6
COMMUNICATION
5
CONVERTER
4
Model
3
SF-232DB3
2
1
DB-9 CONNECTOR
Note: To avoid ground loops, the neutral and safety ground (pin 3) should be connected together
at only one point.

4.2: RS-485

Each EPM 5300P or 5200P instrument has a unique address up to four digits long. This allows the user
to communicate with up to 10,000 instruments. Available standard baud rates are 1200, 2400, 4800, and
9600. To select the proper baud rate, apply the following rules:
The unit operates up to 9600 baud. For a smaller number of instruments over a long distance, use a
lower baud rate. Optimal recommended baud rate is 1200 baud, if noisy conditions exist.
GE Multilin
BACK VIEW
11
12
13
20
21
22
23
24
25
26
27
28
A DIRECT PIN-TO-PIN CABLE CAN BE USED.
NO NULL MODEM IS REQUIRED.
Figure 4.1: RS-232C Communication Connection Installation
EPM 5000 series Advanced Power Meters
CHAPTER 4: COMMUNICATION INSTALLATION
RS-232 COMMUNICATION CONNECTION
CONNECTION FOR DB-9 FEMALE
PIN 2 - RECEIVE OF THE HOST/COMPUTER
PIN 3 - TRANSMIT OF THE HOST/COMPUTER
PIN 5 - GROUND OF THE HOST/COMPUTER
5 4 3 2 1
9 8
7
DETAIL OF DB-9
6
LAPTOP
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Epm 5200Epm 5350

Table of Contents