4.3: Network of Instruments and Long Distance Communication
The RS-485 Transceiver is required for a large network of instruments.
In a two-wire connection, a maximum of 900 instruments can be included in the same network
(Figure 4.7)
In a four-wire connection, a maximum of 3600 instruments can be included in the same network
(Figure 4.8).
DEVICE
32 UNITS
DEVICE
32 UNITS
Figure 4.7: 2-Wire RS-485 Communication Installation Connection with Transceiver
DEVICE
32 UNITS
DEVICE
32 UNITS
Figure 4.8: 4-Wire RS-485 Communication Installation Connection with Transceiver
Use modems (dedicated or dial-up) when the instruments are located at great distances. However, set
the modem to auto answer at the recommended value of 1200 baud rate, if noise conditions exist. Also,
flow control must be disabled.