Toshiba 1600XP Specifications page 8

Single phase uninterruptible power systems
Hide thumbs Also See for 1600XP:

Advertisement

1600XP Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 5.0 October 2013
3.6kVA – 22kVA
Height:
Weight:
Depth:
Width:
Height:
8.2 Cable Entry:
The UPS is provided with cable entry at the bottom rear of the UPS enclosure.
8.3 Ventilation and Maintenance Requirements:
The UPS requires the following minimum space for ventilation and
maintenance: 28" (front), 18" (top), 6" (rear), and 0" (side).
9.0 External Communications
9.1
EPO Control
The UPS comes equipped with terminals for receiving an emergency power-off (EPO) command
via its closed-contact switch located on its terminal block.
9.2
DB9 Dry Contacts
This is a standard feature that is offered on all the 1600XP models. This feature has a limited
amount of status that can be monitored remotely, but it stills offers the most vital alarms and
faults signals. The dry contacts offer the following alarms/faults:
1)
2)
3)
4)
5)
6)
9.3 RS232-C Communication Interface for factory use.
10.0 Reliability
Mean Time Between Failures (MTBF) of 80,000 hours.
11.0 Conformance
The UPS Complies with UL 1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001,
ISO 14001, NEMA/PE1-1993, RoHs
12.0 Warranty
28 in.
1600XP 14kVA-22kVA UPS
771 lbs.
36 in.
18 in.
36 in.
Fault Signal
Normal Input Power Supply
Bypass Operation
Battery Voltage Drop (Low Battery)
UPS Operation (Closed while on normal operation)
Power Failure
Page 8 of 9