1600XP Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 5.0 October 2013
3.6kVA – 22kVA
Frequency Range
Power Factor
Input Capacity
Input Current Limit
Input Current THD
* Based on typical 70% load. For continuous operation at -30%, de-rate the maximum operating
temperature to 90 F (32 C.)
5.2 UPS Output
Rated Voltage
Output Voltage Requirements
Output Capacity
Rated Load Power Factor
Efficiency
Voltage Regulation
Rated Frequency
Frequency Regulation
Frequency Sync. Range
Voltage Transients
Transient Voltage Recovery
Overload Cap. (on inverter)
Overload Cap. (on Bypass)
Crest Factor
Harmonic Voltage Distortion
1600EP/XP Efficiency
100% Load
75% Load
50% Load
25% Load
: 45 - 65 Hz
: > 0.95 lagging
: 110% of UPS Output Capacity
: 125% of nominal capacity
: < 5% Total Harmonic Distortion (THD)
: 120/208/240 VAC Single Phase
: 1 Phase, 3 Wires + Ground
:
kVA
3.6 kVA
6 kVA
8 kVA
10 kVA
14 kVA
18 kVA
22 kVA
: 0.85 lagging
: Typical: 85%, Minimum: 83% (AC/AC)
: +/- 3% nominal (balanced load)
: 50/60 Hz (Autosensing or manually selectable)
: +/- 0.5, 1.0, or 1.5 Hz
: +/- 1.0 Hz
: +/- 8% (100% step load change)
: +/- 3% (loss or return of input power)
: 50ms maximum to within 2% of nominal
: 125% for 30 sec.,
: 150% for 10 sec.
: 1000% for 1 cycle
: 3.0
: 3% THD @ 100% linear load
: 6% THD @ 100% Non-linear
Efficiency Vs. Load Table
3.6kVA
6kVA
8kVA
84.9%
84.9%
84.9%
84.9%
84.9%
84.9%
83.4%
83.4%
83.4%
75.7%
75.7%
75.7%
Page 5 of 9
kW (@ 0.85PF)
3.1 kW
5.1 kW
6.8 kW
8.5 kW
11.9 kW
15.3 kW
18.7 kW
10kVA
14kVA
18kVA
84.9%
84.9%
84.9%
84.9%
84.9%
84.9%
83.4%
83.4%
83.4%
75.7%
75.7%
75.7%
22kVA
84.9%
84.9%
83.4%
75.7%