Download Print this page

Toshiba 1600XP Specifications page 4

Single phase uninterruptible power systems
Hide thumbs Also See for 1600XP:

Advertisement

1600XP Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 5.0 October 2013
3.6kVA – 22kVA
4.3.3 Static Bypass Switch
1) TRANSFER - The static bypass switch consists of thyristor switches in conjunction
with an output contactor to permit manual switching from bypass to UPS and UPS to
bypass without power interruption. The UPS instantaneously transfers to bypass should
a component fail during normal operation (provided the UPS and bypass are in
synchronization). Auto-retransfer to UPS after an overload condition is completed
within one second after the bus has dropped to 100% of nominal.
2) REMOTE RUN/STOP - A set of normally open dry contacts are provided to remotely
transfer the UPS on-line and off-line. When the UPS is in this mode of operation, the
UPS front control panel is disabled to provide a secured configuration.
4.3.4 Microprocessor Control System
1) DESCRIPTION - The UPS system is provided with a microprocessor internal control
system to perform start-up, transfers, monitoring, and battery recharging.
microprocessor provides information to the user (via a touch screen liquid crystal display
with searchable menu tree) such as system status, fault messages and input and output
parameters.
2) LED INDICATORS - The following LED indicators are provided on the UPS front
panel displays, which mimic power flow through the UPS:
3) SYSTEM METERING - The UPS is provided with a touch screen display which can
display current system operation, monitor current operating mode, performance settings,
or fault/ incident records.
4) SYSTEM DIAGNOSTICS - Should a fault occur during operation, diagnostic
information is displayed in the lower left corner of the touch screen.
5) Battery Test Function
The UPS is provided with a "Battery Test" pushbutton to periodically check the
condition of the batteries. Upon detection of a battery problem, the UPS shall notify the
user of this condition allowing the user to perform a detailed check of the battery string.
5.0 System Parameters
5.1 UPS Input
Input Voltage
Input Voltage Requirement
Input Voltage Variation
Rated Frequency
a) AC INPUT (Green Lamp) - Lights when normal AC input power is being
supplied to the unit.
b) WARNING (Amber Lamp) – Lamp is OFF when the UPS is normal.
c) ON-LINE FAULT (Green/Red Lamp) – GREEN when voltage is within
specifications, and RED when voltage is out of specifications
: 208/240VAC Single Phase
: 2 Wires + Ground
: +10% to -30% *
: 50/60 Hz
Page 4 of 9
The

Advertisement

loading

This manual is also suitable for:

1600xp series