N-TRON SWITCH GROUNDING TECHNIQUES
The grounding philosophy of any control system is an integral part of the design. N-Tron switches are
designed to be grounded, but the user has been given the flexibility to float the switch when required. The
best noise immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to
earth ground via a drain wire (20 gauge minimum size wire). Some N-Tron switches have metal din-rail
brackets that can ground the switch if the din-rail is grounded. In some cases, N-Tron switches with metal
brackets can be supplied with optional plastic brackets if isolation is required.
As an alternate, users can run a drain wire & lug from any of the
Din-Rail screws or empty PEM nuts on the enclosure.
using an unused PEM nut to connect a ground lug via a machine
screw, care should be taken to limit the penetration of the outer
skin by less than 1/4 in (NOTE: Recommend #6 32X1/4"
Phillips pan head zinc screw). Failure to do so may cause
irreversible damage to the internal components of the switch.
Note: Before applying power to the grounded switch, you must
use a volt meter to verify there is no voltage difference between
the power supply's negative output terminal and the switch
chassis grounding point.
If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to
prevent ground loops and interfere with low level signals (i.e. thermocouples, RTD, etc.). Cat5e cables
manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.
In the event all Cat5e patch cable distances are small (i.e. All Ethernet devices are located in the same local
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated
to chassis ground at both ends in systems void of low level analog signals.
(Revised 2013-06-21)
Both V- legs of the power input connector are connected
to chassis internally on the PCB. Connecting a drain wire
to earth ground from one of the V- terminal plugs as
shown here will ground the switch and the chassis. The
power leads from the power source should be limited to 3
meters or less in length.