Output Signal Setting - Mitsubishi Electric FR-A7AY Instruction Manual

Hide thumbs Also See for FR-A7AY:
Table of Contents

Advertisement

EXTENSION ANALOG OUTPUT
4.5.3

Output signal setting

Set the output signals to be monitored. Set Pr. 306 to output the same signal from terminals AM0 and AM1
and Pr. 306 and Pr. 310 to output different signals. For details of signal definitions, refer to Pr. 54 and Pr. 158
of the inverter manual (applied).
Pr. 306/Pr. 310
Types of Monitor
Setting
1
Output frequency
2
Output current
3
Output voltage
5
Frequency setting
6
Running speed
8
Converter output voltage
9
Regenerative brake duty
*1
Electronic thermal relay
10
function load factor
11
Output current peak value
Converter output voltage
12
peak value
13
Input power
14
Output power
17
Load meter
21
Reference voltage output
24
Motor load factor
50
Power saving effect
52
PID set point
53
PID process value
*1
Setting can be made only for the 75K(01800-EC, S75K-CH) or more.
*2
The setting depends on capacities. (55K (01160-EC, 55K-CH) or less/75K (01800-EC, S75K-CH) or more.)
18
Increments
0.01Hz
0.01A/0.1A
*2
0.1V
0.01Hz
1(r/min)
0.1V
0.1%
0.1%
0.01A/0.1A
*2
0.1V
0.01kW/0.1kW
*2
0.01kW/0.1kW
*2
0.1%
0.1%
Variable according to parameters Inverter capacity
0.1%
0.1%
Full-Scale Value
Pr. 55
Pr. 56
800V
Pr. 55
The value converted with the Pr. 37 value from Pr. 55.
800V
Pr. 70
Electronic thermal relay function operation level
Pr. 56
800V
Rated inverter power × 2
Rated inverter power × 2
Pr. 56
200%
100%
100%