Calibration Of Meter - Mitsubishi Electric FR-A7AY Instruction Manual

Hide thumbs Also See for FR-A7AY:
Table of Contents

Advertisement

EXTENSION ANALOG OUTPUT
4.5.2

Calibration of meter

(1) Outputting the same select signals from terminals AM0 and AM1 (Pr. 309 = 0 or 10)
START
Connect a DC voltmeter (or DC ammeter) across
terminals AM0 (or terminal AM1) and AMC.
Use Pr. 323 (Pr. 324) to calibrate the meter
when the voltage (current) input is 0.
Set "21" (reference voltage output) in Pr. 306.
Run the inverter
Use Pr. 901 to perform adjustment, then set.
END
In Pr. 306, set the types of the signals to be output.
(Refer to page 18.)
CAUTION
1.
If calibration is made without "21" (reference voltage output) set in Pr. 306, Terminals FM/AM of the inverter
is calibrated. To calibrate the extension analog output, always set "21" in Pr. 306.
2.
When the plug-in option used was remounted on other inverter, use Pr. 323 and Pr. 324 to calibrate again.
16
At this time, check that the polarity is correct
If the meter needle does not point to 0 when voltage or current input is 0,
use Pr. 323 AM0 0V adjustment or Pr. 324 AM1 0mA adjustment to
calibrate the meter
At this time, the following analog signal is actually output and deflects the meter.
<across terminals AM0-AMC>
Maximum output voltage set previously (factory setting: 10VDC)
<across terminals AM1-AMC>
Maximum output current set previously (factory setting: 20mADC)
press
to set.

Advertisement

Table of Contents
loading

Table of Contents