Table 2–10 gives the environmental specifications of the systems.
Table 2–10 GS80/160/320 Environmental Specifications
Variable
Temperature
Operating
Nonoperating
Relative humidity (noncondensing)
Operating
Nonoperating
Maximum altitude
Operating
Nonoperating
Minimum clearances
Front operating
Front service
Rear operating
System and power cabinets
Expander cabinet
Rear service
Left side operating
Left side service
Right side operating
Right side service
2-12
AlphaServer GS80/160/320 Site Preparation
Specification
5 to 35º C (41 to 95º F)
–40 to 66º C (–40 to 151º F)
10–90%
10–95%
3050 m (10,000 ft)
12,200 m (40,000 ft)
75 cm (29.5 in.)
75 cm (29.5 in.)
75 cm (29.5 in.)
15 cm (6.0 in.)
75 cm (29.5 in.)
None
75 cm (29.5 in.)
None
None