6.5.

Program example for monitoring the output frequency

Example 5 shows
Output frequency reading code number: 0001H (hexadecimal)
When the output frequency is 50Hz, D1 is 1388H (5000) (unit: 0.01Hz).
X0
X0F
M0
X20
Refer to 5.5.11 for detail.
a ladder logic to
SW80.0
X1
[ MOV H1 W100]
X100C
Example 5
read the output frequency of station 1 inveter to D1.
( M0)
Check the ready of the station 1
Set monitor code (H0001) of output
frequency to RWw0.
Turn on the monitor command (RY0C)
( Y100C)
[ MOV W1 D1]
Read output frequency (RWr0) to D1
[ END]
when the monitoring flag (RX0C) turns on.
- 41 -
E658130