5.5.2. Double setting is selected (CC-Link Ver.2) (c122=1)

This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 1, there are remote I/O (RX, RY both 32 bits(same as CC-LINK
Ver.1)) and the remote register (RWw, RWr both 8 word) in the communication data for one
station area.
* Default value of RY and RX is 0.
Remote register (Default value = 0)
RWr
Address
RWr n
Monitor value 1
Monitor value 2
RWr n+1
(output frequency)
RWr n+2
Reply code
RWr n+3
Read data
RWr n+4
Monitor value 3
RWr n+5
Monitor value 4
RWr n+6
Monitor value 5
RWr n+7
Monitor value 6
"n" is depend on the station number.

5.5.3. Quadruple setting is selected (CC-Link Ver.2) (c122=2)

This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 2, there are remote I/O (RX, RY both 32 bits(same as CC-LINK
Ver.1)) and the remote register (RWw, RWr both 16 word) in the communication data for one
station area.
* Default value of RY and RX is 0.
Remote register (Default value = 0)
RWr
Address
RWr n
Monitor value 1
Monitor value 2
RWr n+1
(output frequency)
RWr n+2
Reply code
RWr n+3
Read data
RWr n+4
Monitor value 3
RWr n+5
Monitor value 4
RWr n+6
Monitor value 5
RWr n+7
Monitor value 6
Upper 8
Bits
RWr n+8
Lower 8
Bits
RWr n+9
Trip information (output frequency)
RWr n+A
Trip information (output current)
RWr n+B
Trip information (output voltage)
RWr n+C
Trip information (energization time)
RWr n+D
Reserved*
RWr n+E
Reserved*
RWr n+F
Reserved*
"n" is depend on the station number.
* The bit described "
Reserved
** Do not use it.
Inverter → PLC
Signal
Inverter → PLC
Signal
Trip history No.
Trip code
" is unstable. Don't use the "
RWw
Address
RWw n
Monitor code (1 and 2)
RWw n+1
Set frequency
RWw n+2
Instruction code
RWw n+3
Write data
RWw n+4
Monitor code 3
RWw n+5
Monitor code 4
RWw n+6
Monitor code 5
RWw n+7
Monitor code 6
RWw
Address
RWw n
Monitor code (1 and 2)
RWw n+1
Set frequency
RWw n+2
Instruction code
RWw n+3
Write data
RWw n+4
Monitor code 3
RWw n+5
Monitor code 4
RWw n+6
Monitor code 5
RWw n+7
Monitor code 6
Upper 8
Bits
RWw n+8
Lower 8
Bits
RWw n+9
Reserved**
RWw n+A
Reserved**
RWw n+B
Reserved**
RWw n+C
Reserved**
RWw n+D
Reserved**
RWw n+E
Reserved**
RWw n+F
Reserved**