Toshiba TOSVERT VF-S15 series Function Manual page 24

Tosvert vf-s15 series cc-link option unit
Hide thumbs Also See for TOSVERT VF-S15 series:
Table of Contents

Advertisement

2. Input signal (Inverter -> Master)
The following shows input signals to the master unit. (The output signals for the inverter.)
Device No..
RXn0
Forward running
RXn1
Reverse running
Output terminal function 1
RXn2
(RY-RC)
RXn3
Output terminal function 2 (OUT)
RXn4
Output terminal function 3 (FL)
RXn5
Failure FL
RXn6
PI control OFF
Acceleration/ deceleration
RXn7
pattern selection (1 or 2)
RXn8
Emergency stop
RXn9
Coast stop (ST = OFF)
RXnA
Alarm
RXnB
Reserved*
RXnC
Monitoring flag
Frequency setting completion flag
RXnD
(RAM)
RXnE
Reserved*
Instruction code execution
RXnF
completion flag
RX(n+1)0
Reserved*
to RX(n+1)9
RX(n+1)A
Error status flag
RX(n+1)B
Remote station ready
RX(n+1)C
Reserved*
to RX(n+1)F
"n" is depend on the station number.
* The bit described "
Reserved
Signal
OFF: Other than forward running
ON : Forward running
OFF: Other than reverse running
ON : Reverse running
The function depends on output terminal function selection 1
(f130).
The function depends on output terminal function selection 2
(f131).
The function depends on output terminal function selection 3
(f132).
OFF : No failure
ON : Failure
OFF : PI control permitted
ON
OFF: Acceleration/deceleration pattern 1 (AD1)
ON : Acceleration/deceleration pattern 2 (AD2)
ON : Emergency stop
OFF : ST = ON
ON : ST = OFF
OFF: No alarm
ON : Alarm issued
Reserved*
Switched on when the monitored values are set to RWrn,
RWrn+1, RWrn+4 to RWrn+7 by the monitor command
(RYnC) switching on. Switched off when the monitor
command (RYnC) is switched off.
Switched on when the set frequency is written to the inverter
by the frequency setting command (RYnD) switching on.
Switched off when the frequency setting command (RYnD)
is switched off.
Reserved*
Switched on completion of the processing corresponding to
the instruction code (RWw+2) which is executed when the
instruction code execution request (RYnF) switches on.
Switched off when the instruction code execution completion
flag (RXnF) is switched off.
Reserved*
Switched on when occurred an inverter error or option error
(watchdog error, CPU error, ROM error or RAM error).
It is not switched on besides that.
Switched on when the inverter goes into the ready status on
completion of initial setting after power-on or hardware reset.
(Used as an interlock for read/write from/to the master.)
Switched off when an inverter error occurs (protective
function is activated).
Reserved*
" is unstable. Don't use the "
- 23 -
Description
(during stop or reverse rotation)
(during stop or forward rotation)
:
PI control prohibited
Reserved
" bit for the judgment.