Advertisement

5.5.7. Remote Register Assignment

Divide the monitor code (RWw n) into half and select the monitor value 1 (RWr n) from the
lower 8 bits and the monitor value 2 (RWr n) from the higher 8 bits.
For example: When output voltage is selected for the monitor value 1 and output torque is
selected for the monitor value 2. -> The monitor code is 0703H.
* The hexadecimal value attaches and expresses "H" to the end of a number.
1. Remote register (Master -> inverter)
RWw
Address
Signal
Monitor code
RWw n
(1 and 2)
RWwn+1
Set frequency
RWwn+2
Command code 1
RWwn+3
Write data 1
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
RWwn+8
Trip history No.
RWwn+9
to
Reserved
RWwn+F
Set the monitor code to be referenced. By switching on the (RYnC) signal
after setting, the specified monitored data is set to (RWr n).
The monitor value 1 (RWr n): RWw n Setting of the lower 8 bits of monitor
code.
The monitor value 2 (RWr n+1): RWw n Setting of the upper 8 bits of
monitor code.
Set the set frequency. After setting the register, a frequency is written
after turning on (RynD). When the writing of the frequency is completed,
(RXnD) turns on, depending on the input command.
Unit: 0.01Hz
Set the command code for actions such as operation mode switching,
parameter read, write, error reference, error clear, etc. The command will
be executed by turning (RynF) on after the register setting is completed.
When the command execution is completed, (RXnF) turns on.
Set data specified by the above-mentioned command code
(if necessary).
If no data needs to be written, the value shall be zero.
(RynF) is turned on after setting the above-mentioned command code
and this register.
Set the monitor code to be monitored. By setting "ON" in (RYC) after
setting, the specified monitored data is stored in RWr n+4.
Set the monitor code to be monitored. By setting "ON" in (RYC) after
setting, the specified monitored data is stored in RWr n+5.
Set the monitor code to be monitored. By setting "ON" in (RYC) after
setting, the specified monitored data is stored in RWr n+6.
Set the monitor code to be monitored. By setting "ON" in (RYC) after
setting, the specified monitored data is stored in RWr n+7.
Set how many fault records in past to be read.
Upper 8 bits: H00 (latest fault) to H07 (eight faults in past)
Lower 8 bits: H00
Reserved
- 24 -
Description
E658130