5.5.8. Instruction Codes

Code No.
Command mode selection
1003H
read
Command mode selection
2003H
write
Frequency setting mode
1004H
selection read
Frequency setting mode
2004H
selection write
0072H
Special monitor
Special monitor code read
read
0073H
Special monitor selection
write
00F3H
0074H
Trip history No.1, No.2 read
0075H
Trip history No.3, No.4 read
0076H
Trip history No.5, No.6 read
0077H
Trip history No.7, No.8 read
Frequency command value
006DH
(RAM) read
Option frequency command
00EDH
value (EEPROM&RAM) write*
00F4H
Trip history clear
00FCH
Parameter all clear
00FDH
Inverter reset
1000H to 1999H
Read parameters (RAM)
(1000H to
1F99H)
Write parameters
2000H to 2999H
(EEPROM&RAM) *
Item
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: No function
4: Communication option
0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: No function
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
0000H to FFFFH:
Monitor value selected after choosing instruction code 00F3H.
Read the content that was monitored by special monitor.
Select the monitor code of special monitor.
Read the No.1 and No.2 of trip information.
Read the No.3 and No.4 of trip information.
Read the No.5 and No.6 of trip information.
Read the No.7 and No.8 of trip information.
Read the frequency command value (RAM).
Write the option frequency command value (EEPROM &RAM).
9696H: Clear all trip histories.
9696H: Clear all parameters. (Parameters other than
proofreading values are made into factory default settings.)
9696H: Reset the inverter.
To read parameters f000 to f984, add the triple figures
that follow Fxxx to 1000H.
(Ex: f984 -> 984 + 1000 = 1984)
No error occurs when you select 1A00 to 1F99.
Because these parameters are for maintenance.
To write parameters f000 to f984, add the triple figures
that follow Fxxx to 2000H.
Description
- 28 -
E658130