5.

Functions

This option is a communication interface unit that allows the PLC program to operate, monitor
and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate
with a maximum speed of 10Mbps not only transmitting bit data but also by word data.
Moreover, more data transmissions are possible by the use of CC-Link V2.0.

5.1. Initial setting

Set the following parameters of the inverter.
Title
Function
cmod
Command mode
selection
Frequency
fmod
mode selection 1
Number of motor
pole for
f856
communication
Communication
f899
function reset
*Set parameter according to number of motor pole used.
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communcation option
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
setting
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: -
1: Reset (after execution: 0)
- 12 -
Description
E658130
Factory
CC-Link
setting
setting
1
4
0
7
2
*
0
-