Mount The Termination Module - Trane Tracker Version 12 Hardware Installation

Building automation system
Table of Contents

Advertisement

®
Figure 12. Termination module conduit access and mounting holes
Holes for mounting on a 2 in. x 4 in.
conduit box horizontally
(left and right)
Two holes for mounting on a wall
(one on each side)
Holes for mounting on a
4 in. x 4 in. conduit box
(four corners)
BMTK-SVN01D-EN

Mount the termination module

After selecting a suitable location for the Tracker controller, mount the
termination module. Mounting consists of securing the termination
module to a wall or a 2 in. × 4 in. recessed conduit box (mounted vertically
or horizontally) or a 4 in. × 4 in. recessed conduit box (several European
electrical box sizes are also usable) and installing electrical conduit
(optional). Figure 12 shows the conduit access and mounting holes on the
termination module.
Conduit connector
Jamb nut
(attaches to
conduit connector)
Mount the termination module
Conduit access
(three places)
Termination board
Holes for mounting on a 2 in. x 4 in.
conduit box vertically
(top and bottom)
19