Tracker controller specifications
Table 1 shows the specifications for the Tracker controller.
Table 1. Tracker Controller specifications
Specification
Power
Operating environ-
ment
Storage environment
Cabinet
Mounting
Dimensions
Weight
Analog input
•
Thermistor
Binary inputs
•
Utility pulse meter
•
Priority shutdown
Binary output
•
Alarm relay
Memory backup
Approvals
Tracker controller specifications
Description
24 Vac nominal (19 Vac to 30 Vac),
50/60 Hz, 1 phase 40 VA minimum,
UL Class 2 transformer required
From 32°F to 122°F (0°C to 50°C)
10% to 90% relative humidity, non-condensing
From –40°F to 185°F (–40°C to 85°C)
5% to 95% relative humidity, non-condensing
NEMA 1 resin enclosure—plenum rated
Flat wall surface with one of the following recessed
conduit boxes:
2 in. × 4 in.
(5.08 cm × 10.15 cm)
4 in. × 4 in.
(10.15 cm × 10.15 cm)
Height: 8.75 in.
(22.38 cm)
Width:
10.25 in. (26.04 cm)
Depth:
2.75 in.
(6.99 cm)
2.5 lb
(1.13 kg)
10 kΩ at 77°F (25°C)
From –50°F to 200°F (–46°C to 93°C)
User-supplied dry contacts only. Tracker-supplied
voltage of 12 Vdc nominal (10 Vdc to 14 Vdc) at
12 mA nominal (10 mA to 14 mA).
Tracker-supplied single-pole single-throw (SPST) dry
contact rated at 24 Vac, 0.5 A maximum
At power loss, the system backs up memory and
stores all data for seven days. After seven days,
trends and alarms are not retained.
See Appendix B, Declaration of Conformity.