Trane LonWorks TR1 Series VFD Installation And Operation Manual page 25

Variable frequency drive
Hide thumbs Also See for LonWorks TR1 Series VFD:
Table of Contents

Advertisement

Network
Control Word
Drive
The input network variable nviControlWord is
a 16-bit word that provides additional
Control
operational control of the drive, as listed in the
Input
table below. The settings shown represent the
(continued)
Coast Stop command. The Control Word is
not supported by Tracer Summit.
v‡


!
"
#
$
%
&
'
(

!
"
#
$
Drive always stops and ignores
serial bus commands to run when
OFF/STOP function is activated
from drive keypad.
Precedence of the stop commands is:
Coast stop
The drive output stops immediately and the
motor coasts to a stop.
• Drive display show UN.READY (unit
• Drive cannot run in any mode.
• Parameter 503, Coasting stop,
Tr‡‡vt


Q…r†r‡ÃSrsÃGT

Q…r†r‡ÃSrsÃHT
98Ã …hxr
‚Ã98à …hxr

8‚h†‡ÃT‡‚ƒ
‚Ã8‚h†‡ÃT‡‚ƒ
RˆvpxÃT‡‚ƒ
‚ÃRˆvpxÃT‡‚ƒ
A…rr“rÃA…r„
‚ÃA…rr“rÃA…r„

Sh€ƒÃT‡‚ƒ

‚ÃSr†r‡

‚ÃE‚t

‚Ãsˆp‡v‚
†rrÃQh…€Ã'$

Sryh’Ã ÃPAA
Sryh’Ã ÃPI

Sryh’Ã!ÃPAA
Sryh’Ã!ÃPI

Tr‡ˆƒÃGT

Tr‡ˆƒÃHT

‚ÃSr‰r…†vt
Sr‰r…†vt
Control Word Bit Descriptions
for Coast Stop
NOTE
1. Coast stop
2. Quick stop
3. DC brake stop
4. Ramp (Normal) stop
ready) when coast stop is active.
determines interaction with input 27.
Quick stop
The drive output frequency ramps down to
0 Hz according to time set in parameter 207,
Ramp Down Time.
• Drive display shows STOP.
• Drive cannot run in AUTO mode but can
run in HAND mode.
DC brake stop
The drive brakes the motor to a stop using DC
injection braking.
• Parameters 114 and 115 determine
amount and time of DC current applied
for braking.
T‡h…‡
• Drive display shows DC STOP.
Sr†r‡
• Drive cannot run in AUTO mode but can
E‚t
run in HAND mode.
• Parameter 504, DC Brake, determines
interaction with inputs 19/27.
Ramp stop
The drive output frequency ramps down to
0 Hz according to time set in parameter 207,
Ramp Down Time.
• Factory setting is 60 sec for fan
applications and 10 sec for pump
applications.
• Drive display shows STAND BY.
• Drive can run in HAND mode or AUTO
through a digital input command.
• Parameter 505, Start, determines
interaction with input 18.
25