Network Configuration Properties (Nci); Network Drive Control Input - Trane LonWorks TR1 Series VFD Installation And Operation Manual

Variable frequency drive
Hide thumbs Also See for LonWorks TR1 Series VFD:
Table of Contents

Advertisement

Network
The TR1 Series VFD LonWorks option card
Configuration
supports LonMark network design to improve
interoperability.
Properties
(Nci)
The configuration parameters are network
variable inputs to the drive. Configuration of
parameters needs setting only one time, usually
at installation. See the table below for
definitions.
Function
Nom . motor
frequency
Nom . motor rpm
M in. frequency
M ax. frequency
Ram p up time
Ram p down time
Heart beat tim e
Functions listed in the table are part of the LonMark Functional Profile for Variable Speed Drive 6010 starting with
version 1.1
Network
The most common functions for controlling the
Drive
TR1 Series Variable Frequency Drive from the
LonWorks network are made readily available.
Control
Those functions and their descriptions are
Input
presented in the table below. The control word
function accesses additional drive capabilities
for network control. The installer must verify
that parameter 500, Protocol, is set for FC
protocol.
Function
Start/Stop
*Reset fault
Reference 1
Reference 3
Control word
**Drive speed
setpoint
Setpoint 1
Setpoint 2
Bus feedback 1
Bus feedback 2
*
Reset on a transition from 0 to 1. A
**
Part of the LonMark Functional Profile for Variable Speed Drive 6010 starting with version 1.1
Network variable nviDrvSpeedStpt is comprised of a stop/start command (state) and a separate speed command
(value). 0 is a stop command and 1 is a run command. Drive speed is a function of the reference signal between 0
and 100%.
Network Configuration Definitions
SNVT Type
Variable Nam e
SNVT_freq_hz
nciNmlFreq
SNVT_rpm
nciNmlSpeed
SNVT_lev_percent
nciMinSpeed
SNVT_lev_percent
nciMaxSpeed
SNVT_time_sec
nciRampUpTim e
SNVT_time_sec
nciRampDownTim e
SNVT_time_sec
nciSndHrtBt
Network Variable Inputs to TR1 Series VFD
SNVT Type
Variable Name
SNVT_lev_disc
nviStartStop
SNVT_lev_disc
nviResetFault
SNVT_lev_percent nviRefPcnt
SNVT_freq_hz
nviRefHz
SNVT_state
nviControlWord
SNVT_switch
nviDrvSpeedStpt
SNVT_lev_percent nviSetpoint1
SNVT_lev_percent nviSetpoint2
SNVT_lev_percent nviFeedback1
SNVT_lev_percent nviFeedback1
"
"
0
must be sent after reset to enable the next reset.
!
Data written to configuration
parameters is stored in non-
volatile memory. Continuous
writing may impair non-volatile
memory.
Units
1 Hz
1 rpm
0.005%
0.005%
1 sec
1 sec
0.1 sec
The choice of open loop or closed loop operation
of the drive is selected in parameter 100,
Configuration.
For open loop control, it is recommended to
set the following parameters:
201 = 0 Hz
202 = 60 Hz
203 = LINKED TO HAND/AUTO
204 = 0.0
205 = 60.0
Units
Boolean
Boolean
0.005%
0.1 Hz
16 Boolean
(see below)
0.01%
0.01%
0.01%
0.01%
Parameter
104
106
201
202
207
208
---
Parameter
104
---
---
---
---
Ctrw + Ref.
418
419
535
536
23