Alarm And Status Relay Outputs (Programmable Relays) - Trane CGAM Installation & Operation Manual

Air-cooled scroll chillers 20 - 130 tons
Hide thumbs Also See for CGAM:
Table of Contents

Advertisement

swap" the pumps upon detection of a fault, and may avoid the inevitable Flow Loss diagnostic (and
unit shutdown) that will result if there is no fault feedback.
When configured for Dual Pump Fixed Speed, the CH530 will swap pumps on detection of a fault
(if installed), or when a flow loss or overdue event occurs. It will also switch pumps each time the
overall pump request is removed and re-engaged, unless a fault is detected on one of the pumps.
If faults are detected on both pumps, the unit will be shut down.
In addition to the factory installed flow switch, a field-supplied auxiliary contact is required, so that
the chiller will only detect flow if a pump is running and the flow switch says flow is present.

Alarm and Status Relay Outputs (Programmable Relays)

A programmable relay concept provides for enunciation of certain events or states of the chiller,
selected from a list of likely needs, while only using four physical output relays, as shown in the
field wiring diagram. The four relays are provided (generally with a Quad Relay Output LLID) as part
of the Alarm Relay Output Option. The relay's contacts are isolated Form C (SPDT), suitable for use
with 120 VAC circuits drawing up to 2.8 amps inductive, 7.2 amps resistive, or 1/3 HP and for 240
VAC circuits drawing up to 0.5 amp resistive.
The list of events/states that can be assigned to the programmable relays can be found in
The relay will be energized when the event/state occurs.
Table 36. Alarm and Status Relay Output Configuration Table
Description
This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects either the
Alarm - Latching
Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
This output is true whenever there is any active diagnostic that could automatically clear, that affects either the Chiller,
Alarm - Auto Reset
the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing.
Alarm
This classification does not include informational diagnostics
This output is true whenever there is any diagnostic effecting Refrigerant Circuit 1, whether latching or automatically
Alarm Ckt 1
clearing, including diagnostics affecting the entire chiller. This classification does not include informational diagnostics.
This output is true whenever there is any diagnostic affecting Refrigerant Circuit 2 whether latching or automatically
Alarm Ckt 2
clearing, including diagnostics effecting the entire chiller. This classification does not include informational diagnostics.
Chiller Limit Mode (with
This output is true whenever the chiller has been running in one of the Unloading types of limit modes (Condenser,
a 20 minute filter)
Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 1, and false
Circuit 1 Running
when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 2, and false
Circuit 2 Running
when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on the chiller and false when
Chiller Running
no compressors are commanded to be running on the chiller.
Maximum Capacity
This output is true whenever the chiller has all compressors on. The output is false once one compressor is shut off.
Relay Assignments Using TechView
CH530 Service Tool (TechView) is used to install the Alarm and Status Relay Option package and
assign any of the above list of events or status to each of the four relays provided with the option.
The relays to be programmed are referred to by the relay's terminal numbers on the LLID board
1A18.
The default assignments for the four available relays of the CGAM Alarm and Status Package
Option are:
Table 37. Default Relay Assignments
Relay
Relay 1 Terminals J2 -12,11,10:
Relay 2 Terminals J2 - 9,8,7:
Relay 3 Terminals J2-6,5,4:
Relay 4 Terminals J2-3,2,1:
CG-SVX17D-EN
Installation - Electrical
Compressor Running
Latching Alarm
Chiller Limit Mode
Warning
Table 36.
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents