Table 66. Compressor Locations
Slant Unit
1B
1A

Compressor Replacement

If the CGAM chiller suffers a failed compressor, use these steps for replacement:
Each compressor has lifting eyes. Both lifting eyes must be used to lift the failed compressor. DO
NOT LIFT A COMPRESSOR USING A SINGLE LIFTING EYE. Use proper lifting techniques, a
spreader bar and rigging as for lifting both compressors simultaneously.
Compressor weights by compressor model are:
After a mechanical failure of a compressor, it is necessary to change the oil in the remaining
compressor and also replace the liquid line filter drier. After an electrical failure of a compressor,
it will also be necessary to change the oil in the remaining compressor, replace the liquid line filter
drier and add a suction filter drier with clean-up cores.
Note: Do not alter the refrigerant piping in any way as this can affect compressor lubrication.
Note: Do not add a filter drier within 10 inches of the elbow for CSHD compressors, or within 16
CG-SVX17D-EN
V Unit
2B
2A
CSHD 125 - 142 lbs.
CSHD 161 - 155 lbs.
CSHN 184 - 234 lbs.
CSHN 250 - 238 lbs.
CSHN 315 - 337 lbs.
CSHN 374 - 362 lbs.
inches of the elbow for CSHN compressors.
W Unit
2C
1B
2B
1A
2A
Maintenance
1C
1B