Visonic POWERMAX+ Installer's Manual page 6

Fully supervised wireless alarm control system
Hide thumbs Also See for POWERMAX+:
Table of Contents

Advertisement

6-POSITION
RJ-11 PLUG
TEL
LINE
TEL.
LINE
JACK
FOR ALL
COUNTRIES
EXCEPT
NORTH
AMERICA
HOUSE
PHONES
Notes:
*
Zone 29/GND and Zone 30/GND terminals can be
connected to a normally closed contact of a detector,
switch (for example a Tamper switch of any device), or
a pushbutton, via a 2.2 K
resistor is connected at the factory across both Zone
29/GND and Zone 30/GND terminals. The resistors
should remain there if the terminals are not used. The
V+ terminal can be used to supply 12V (up to
100mA) to a detector (if necessary).
**
Both +12V terminals are identical (shorted together).
The EXT terminal can be used to trigger an external
siren.
The INT terminal can be programmed for an "internal
siren" or "strobe" (see DEFINE OUTPUTS - DEFINE
INT/STRB in par. 4.7).
The +12V and "-Hold" terminals can be connected to
a siren (for constant DC power supply) – not
applicable in North America.
If wired sirens are used, additional tamper zone(s) is
required. This can be accomplished with zones 29 and
30.
*** The X-10 jumper should be in 1-W position (for 1-way
power line interface unit) or in 2-W position (for 2-way
power line interface unit).
WARNING! When plugging terminals back into place, be
sure to align them carefully with the pins on the PCB.
6
OR
RED & GREEN TO "LINE"
BROWN & GREY FOR "SET"
RJ-31X JACK
GRAY
RED
3
4
LINE
FROM
STREET
5 6
GRN
BROWN
FOR INSTALLATIONS IN NORTH AMERICA ONLY
Figure 3.3 - Wiring Diagram
Ω
±5% resistor. Such a
CONNECT WIRED DETECTORS AS FOLLOWS:
Detector with
Tamper switch
TAMP
Alarm
N.C.
N.C.
Power
-
+
2.2
k Ω
(*)
ZONE 29 /
GND
V+
ZONE 29 /
ZONE 30
ZONE 30
(*)
ZONE 29
(*)
GND
(*)
ZONE 30
(*)
V+
(***)
RED
X-10
GREEN
BROWN
GREY
RJ-31X CORD
2
1
8
7
8-POSITION
RJ-31X PLUG
Misaligned or reverse insertion of terminals may damage
internal PowerMax+ circuits!
PGM port can be used to activate a device with limited
current, as defined in the specifications.
IMPORTANT! The terminals for internal and external
sirens are DC outputs intended for 12V sirens. Connecting
a loudspeaker to any of these outputs will cause a short
circuit and will damage the unit.
Notes for UL installations
a. The site INTERNAL SIREN and EXTERNAL SIREN
are suitable for burglar alarm application only. They are
not suitable for fire alarm signaling. If external siren is
used, it must be UL listed and shall be rated to operate
under the voltage specified in the Specifications.
b. A device that is connected to PGM terminal should not
be programmed to be activated during standby.
c. The system shall be installed in accordance with Chapter
2 of the National Fire Alarm Code, ANSI/NFPA 70.
d. All wiring should be acceptable for class 1 systems as defined
by the National Electrical Code, ANSI/NFPA 70. No. 26 AWG
or larger telecommunication line cord shall be used.
e. The system shall be installed in accordance with CSA
C22.1 Canadian Electrical Code, Part 1.
Detector without
Tamper switch
Regarding zones 29 & 30, the Control
Alarm
Panel "sees" a specific resistance
N.C.
Power
according to the event, as follows:
-
+
Normal (no alarm & no tamper): 2.2 kΩ
Alarm event: 4.4 kΩ
Tamper event: Infinite resistance
2.2 k Ω
(*)
GND
V+
(**)
-
HOLD
(**)
EXT
(**)
INT
(**)
+12V
(**)
+12V
PGM
IMPORTANT! OFF-THE-
SHELF CABLES ARE
6-POSITION
UNSUITABLE HERE.
RJ-11 PLUG
PREPARE YOUR OWN
"ONE TO ONE" CABLE.
NOTE: PSC-04 IN THE U.S. AND CANADA,
ALTERNATIVE MODELS ELSEWHERE.
Note
POWER
TRANSFORMER
SITE
9 VAC
EXTERNAL
SIREN
SITE
INTERNAL
SIREN OR
STROBE
POWERLINE
INTERFACE
MODULE
(SEE NOTE)
1
2
3
4
5
6
DE5467IP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents