Electrical
Input Signals
Input Impedance
Input Characterization
Sensitivity
Hysteresis
Deadband
Repeatability
Voltage/ Supply Stability
Temperature Coefficient
Zero Suppression
Input Filters
Solid State Motor Control
Failsafe operation
Feedback signals/Output
Slidewire Emulation
Isolation
Load Requirement (4-20)
Programmable Functions
Specifications – Actuator
Analog: 0/4 to 20 mA (With supplied 250 ohm shunt resistor for current range)
0/1 to 5 Vdc
0 to 10 Vdc
Digital:
Remote Setpoint via Modbus RTU (RS485)
Input
0/4 to 20 mA
0/1 to 5 Vdc
Provides characterization of the input signal.
Selections are: Linear, Square Root or Custom.
0.2 % to 5 % of 90° span, proportional to deadband
Less than 0.4 % of full scale
0.2 % to 5 % of 90° span, adjustable. Shipped at 0.5%
0.2 % of 90° span
0.25 % of span with +10/
-
15 % voltage change
Less than ± 0.030 % of span per degree C for 0 °C to 50 °C
Less than ± 0.05 % of span per degree C for
90% of span
Selectable spike and low pass filters
CW/CCW open collectors (opto-isolators) for use as discrete control inputs to the inverter
for motor operation.
If input signal exceeds configured input range. Selectable and adjustable.
0 to 20 mA, 4 to 20 mA
0 to 5 Vdc, 1 to 5 Vdc with 250 ohm resistor; (0 to 16 Vdc with 800 ohm resistor)
Provides output voltage ratiometric to shaft position and potentiometric to supply voltage
(1 to 20 Vdc) without a slidewire. Emulates a 100 ohm to 1000 ohm slidewire. 10 mA
output maximum.
Input signal, output signal and power are isolated from each other.
Current Out — 0 to 1000 ohms
Selectable and configurable operating parameters:
•
Input range
•
Input filtering
•
Input characterization
•
Security
•
Digital Input action
Input Impedance
250 ohms
10 K ohms
-
30 °C to 65 °C
•
Deadband
•
Failsafe on loss of
input signal
•
Failsafe on loss of
position sensor
•
Direction of rotation
61-86-03-13
Page 7
•
Relay closure
action
•
Communication
parameters
•
Split range
operation
•
Output range
•
Alarms