Honeywell 11280S Specification page 6

Smart actuator
Table of Contents

Advertisement

61-86-03-13
Page 6
Physical
Torque
Model #
lb-ft (N_M)
11284S
425
(576)
11285S
840
(1139)
11286S
1500
(2033)
11288S
2500
(3389)
11289S
4000
(5423)
11287S
5500
(7457)
Electrical
Mains Supply
Motor
Motor Current
Loss of Power
Local Auto - Manual
Switch
Limit Switches
Auxiliary
Switches/Relays
Installation Category
(Overvoltage Category)
Pollution Degree
Specifications – General,
Output
Shaft Key
Shaft Size
Size
2"
1/2"
(51 mm)
(13 mm)
2"
1/2"
(51 mm)
(13 mm)
2"
1/2"
(51 mm)
(13 mm)
2-1/2"
5/8"
(64 mm)
(16 mm)
2-1/2"
5/8"
(64 mm)
(16 mm)
2-1/2"
5/8"
(64 mm)
(16 mm)
115/220 Vac, single phase 50/60 Hz up to 1500 lb-ft
208/200 – 240/380 – 480/575 Vac, three phase 50/60 Hz
Inverter rated, continuous duty, C face mounting
Motor Size
(Horsepower)
½
¾
1
1 ½
2
3
Stays in place
Allows local manual and automatic operation of the actuator
Standard - Two SPDT end-of-travel limits rated 10 A at 125 Vac, 5 A at 250 Vac.
Optional – Up to 2 additional SPDT switches (or 4 relay outputs, programmable)
Category II: Energy-consuming equipment supplied from the fixed installation. Local level
appliances, and industrial control equipment. (EN 61010-1)
Pollution degree 2: Normally non-conductive pollution with occasional conductivity caused by
condensation. (ref. IEC 664-1)
Continued
Output
Maximum
Shaft
Overhang
Length
Load
5"
3700 lb.
(127 mm)
(1678 kg)
5"
3700 lb.
(127 mm)
(1678 kg)
5"
3700 lb.
(127 mm)
(1678 kg)
6"
7500 lb.
(152 mm)
(3402 kg)
6"
7500 lb.
(152 mm)
(3402 kg)
6"
7500 lb.
(152 mm)
(3402 kg)
Full Load Amps (FLA)
@ 230 Vac
1.6
2.2
2.6
4.4
5.6
7.8
Handwheel
Approx.
Diameter
Maximum
Weight
18"
300 lb.
(457 mm)
(136 kg)
18"
300 lb.
(457 mm)
(136 kg)
18"
300 lb.
(457 mm)
(136 kg)
18"
550 lb.
(457 mm)
(251 kg)
18"
600 lb.
(457 mm)
(272 kg)
18"
600 lb.
(457 mm)
(272 kg)
@ 460 Vac
0.8
1.1
1.3
2.2
2.8
3.9

Advertisement