Honeywell T775U Series 2000 Installation Instructions Manual page 26

Electronic stand-alone controller
Hide thumbs Also See for T775U Series 2000:
Table of Contents

Advertisement

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM
MOD 1
SETBACK
Fig. 60. Program - Setback.
PROGRAM
MOD 1
SENSOR
Fig. 61. Program - Sensor.
PROGRAM
MOD1
THROT RNG
Fig. 62. Program - Throttling Range or Differential.
62-0255—07
MENU
2.1.3. SETBACK
PROGRAM
MOD 1
The Setback temperature option displays only if
SETBACK
scheduling is enabled (see Fig. 47 on page 21) or the DI
Option is set to Setback. (see Fig. 49 on page 22).
This is the desired setpoint temperature that you want to
use during setback mode for this output. For example, if
60
o
F
your setpoint is 70°F and you want the temperature to
drop 10°F during setback mode, enter 60°F as the set-
ENTER
point for this output.
SETBACK
SETPOINT
1. From the menu, use the
FOR MOD 1
M24584
light SETBACK.
2. Use the
desired setpoint temperature.
3. Press the
the menu.
MENU
2.1.3. SENSOR
PROGRAM
MOD 1
This sub-menu choice is only available on the T775U2016
SENSOR
model.
SENSOR A
SENSOR B
1. From the menu, use the
light SENSOR A or SENSOR B.
2. Press the
and display the next option.
SELECT
SENSOR
FOR
MOD 1
M28660
MENU
2.1.5. THROTTLING RANGE or
PROGRAM
MOD 1
DIFFERENTIAL
THROT RNG
Throttling Range displays for Modulating outputs.
Differential is used for the Relay outputs.
1. From the menu, use the
light THROT RNG or DIFFERNTL.
20
o
2. Press the
F
value.
3. Use the
ENTER
THROTLLING
desired value.
RANGE FOR
MOD 1
M24582
4. Press the
the next option.
The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.
In heating mode, the Differential is below the setpoint.
The relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint.
The relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
26
and
buttons to high-
and
buttons to increase/decrease the
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
button to accept the value and display
and
buttons to high-
button to accept the sensor selection
and
buttons to high-
button to display the throttling range
and
buttons to increase/decrease the
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
button to accept the value and display

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents