Honeywell T775U Series 2000 Installation Instructions Manual page 15

Electronic stand-alone controller
Hide thumbs Also See for T775U Series 2000:
Table of Contents

Advertisement

SETUP
SENSORS
SENSOR A
TYPE
PT 1000
0-5V
0-10V
4-20MA
SENSOR A
Fig. 27. Setup - Sensors - Sensor A - Type.
SETUP
SENSORS
SENSOR A
UNITS
DEG F
DEG C
Fig. 28. Setup - Sensors - Sensor A - Units.
SETUP
SENSORS
SENSOR A
UNITS
DEG F
DEG C
PSI
IN WC
% RH
PA
KPA
PPM
NONE
UNITS FOR
SENSOR A
Fig. 29. Setup - Sensors - Sensor A - Units.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
1.2.2.1. TYPE
SETUP
SENSORS
1. From the Sensor A selections, use the
SENSOR A
TYPE
buttons to highlight TYPE.
2. Press the
3. Use the
value PT1000 (1097
20MA.
Default: PT1000
NOTE: The default label PT1000 refers to a 1097 PTC
temperature sensor.
SELECT
TYPE FOR
4. Press the
M24589A
the Sensor A selections.
5. For PT1000 (1097 PTC) temperature sensors, go
to "1.2.2.2.1. UNITS (Sensor A or B; PT1000
[1097W PTC)]".
For 0-5V, 0-10V, and 4-20MA sensors, go to
"1.2.2.2.2. UNITS (Sensor A only; 0-5V, 0-10V, or 4-
20mA)"
SETUP
1.2.2.2.1. UNITS
SENSORS
SENSOR A
[1097 PTC)]
UNITS
If Sensor A is configured for °F or °C units, then the units
selection does not appear for Sensor B, since Sensor B
uses the units specified for Sensor A.
1. From the Sensor A selections, use the
buttons to highlight UNITS.
2. Press the
3. Use the
SELECT
Default: F (Fahrenheit)
UNITS FOR
4. Press the
SENSOR A
M24590
the Sensor A selections.
Continue with "1.2.2.3. CALIBRATE (Sensor A or B)".
SETUP
1.2.2.2.2. UNITS
SENSORS
SENSOR A
4-20mA)
UNITS
1. From the Sensor A selections, use the
buttons to highlight UNITS.
2. Press the
3. Use the
and highlight the desired unit of measure.
You may need to scroll up or down to view all units.
Default: F (Fahrenheit)
SELECT
4. Press the
the Sensor A selections.
M24591A
15
(Sensor A only)
and
button to display the type values.
and
buttons to highlight the desired
PTC), 0-5V, 0-10V, or 4-
button to accept the units and return to
(Sensor A or B; PT1000
and
button to display the temperature units.
and
buttons to highlight F or C.
button to accept the units and return to
(Sensor A only; 0-5V, 0-10V, or
and
button to display the units list.
and
buttons to scroll through the list
button to accept the units and return to
62-0255—07

Hide quick links:

Advertisement

Table of Contents
loading