Honeywell T775U Series 2000 Installation Instructions Manual page 18

Electronic stand-alone controller
Hide thumbs Also See for T775U Series 2000:
Table of Contents

Advertisement

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
OUTPUTS
MOD 1
Fig. 36. Setup - Outputs - Modulating Output Menu.
SETUP
OUTPUTS
MOD 1
TYPE
Fig. 37. Setup - Outputs - Mod Out - Type.
SETUP
OUTPUTS
MOD 1
MIN OUT %
Fig. 38. Setup - Outputs - Mod Out - Minimum Output
Percentage.
SETUP
OUTPUTS
MOD 1
INTEGRAL
Fig. 39. Setup - Outputs - Mod Out - Integral.
62-0255—07
1.3.1. Setting up the Modulating Outputs
SETUP
OUTPUTS
MOD 1
1. From the Output menu, use the
highlight the desired modulating output (MOD 1 or
TYPE
MIN OUT %
MOD 2).
INTEGRAL
2. Press the
DERIVATIV
menu.
SCHEDULE
RESET
EXIT
Use the remaining procedures, beginning with "1.3.1.1.
TYPE (of output signal)", to set up each modulating
output. If you have two modulating outputs, repeat these
procedures for each modulating output.
M24599
SETUP
1.3.1.1. TYPE (of output signal)
OUTPUTS
MOD 1
1. From the Mod menu, use the
TYPE
highlight TYPE.
4 - 20 mA
0-10 V
2. Press the
2-10 V
3. Use the
SERIES 90
output type.
4. Press the
return to the Mod menu.
SELECT
TYPE FOR
MOD 1
M24600
SETUP
1.3.1.2. MIN OUT %
OUTPUTS
MOD 1
The minimum output % prevents the output from dropping
MIN OUT %
below the value entered. This value can be useful to
maintain minimum damper position.
Using the time clock or digital input to disable the output
forces the output to 0%.
0
%
1. From the Mod menu, use the
ENTER
highlight MIN OUT %.
MINIMUM
2. Press the
PERCENT FOR
3. Use the
MOD 1
M24601
desired value from 0% to 100% in 1% increments.
4. Press the
return to the Mod menu.
SETUP
1.3.1.3. INTEGRAL
OUTPUTS
MOD 1
1. From the Mod menu, use the
INTEGRAL
highlight INTEGRAL.
2. Press the
3. Use the
value from 0 to 3,600 in 10 second increments.
400
SEC
4. Press the
ENTER
INTEGRAL
return to the Mod menu.
TIME FOR
MOD 1
M24602
See the Notes on page 19 for Integral timing information.
18
and
button to display the selected MOD
and
button to display the Type selections.
and
buttons to highlight the desired
Default: 4-20 mA
button to accept the selected type and
and
button to display the Min Out %.
and
buttons to increase/decrease the
Default: 0%
Range: 0 to 100%
button to accept the percentage and
and
button to display the Integral seconds.
and
buttons to increase/decrease the
Default: 400 seconds
Range: 0 to 3,600 seconds
button to accept the seconds and
buttons to
buttons to
buttons to
buttons to