Teledyne 3000TB Instruction Manual page 57

Trace oxygen analyzer
Hide thumbs Also See for 3000TB:
Table of Contents

Advertisement

Trace Oxygen Analyzer
Chapter 3, Installation and/or the Interconnection Diagram included at the
back of this manual for relay terminal connections.
The system failure alarm has a fixed configuration described in chapter
3 Installation.
The concentration alarms can be configured from the front panel as
either high or low alarms by the operator. The alarm modes can be set as
latching or non-latching, and either failsafe or non-failsafe, or, they can be
defeated altogether. The setpoints for the alarms are also established using
this function.
Decide how your alarms should be configured. The choice will depend
upon your process. Consider the following four points:
1. Which if any of the alarms are to be high alarms and which if any
2. Are either or both of the alarms to be configured as failsafe?
3. Are either of the alarms to be latching?
4. Are either of the alarms to be defeated?
are to be low alarms?
Setting an alarm as HIGH triggers the alarm when the oxygen
concentration rises above the setpoint. Setting an alarm as LOW
triggers the alarm when the oxygen concentration falls below the
setpoint.
Decide whether you want the alarms to be set as:
Both high (high and high-high) alarms, or
One high and one low alarm, or
Both low (low and low-low) alarms.
In failsafe mode, the alarm relay de-energizes in an alarm
condition. For non-failsafe operation, the relay is energized in an
alarm condition. You can set either or both of the concentration
alarms to operate in failsafe or non-failsafe mode.
In latching mode, once the alarm or alarms trigger, they will
remain in the alarm mode even if process conditions revert back
to non-alarm conditions. This mode requires an alarm to be
recognized before it can be reset. In the non-latching mode, the
alarm status will terminate when process conditions revert to non-
alarm conditions.
The defeat alarm mode is incorporated into the alarm circuit so
that maintenance can be performed under conditions which
would normally activate the alarms.
The defeat function can also be used to reset a latched alarm.
(See procedures, below.)
Teledyne Analytical Instruments
Operation 4
4-17

Advertisement

Table of Contents
loading

Table of Contents